 "manufacturer": "Lynxspring",
 "manufacturer_slug": "lynxspring",
 "model": "BZ424-LX configurable VAV controller (Onyxx LX)",
 "model_slug": "bz424-lx",
 "aliases": [
  "BZ424-LX",
  "BZ424",
  "Onyxx LX BZ424",
  "Onyxx LX VAV controller 4 UI"
 ],
 "equipment_type": "VAV box controller",
 "applies_to": "Lynxspring Onyxx LX BZ424-LX configurable VAV controllers (4 UI, 2 AO, 4 BO, built-in actuator) on BACnet MS/TP.",
 "summary": "The BZ424-LX is the larger configurable VAV controller in the Onyxx LX range, with four universal inputs, two analog and four binary outputs and an integrated damper actuator and airflow sensor. Its fixed BACnet MS/TP map covers airflow and damper control, zone setpoints for up to three zones, humidity, CO2 and dewpoint/condensation logic, five auxiliary outputs, PID loops and configuration multi-states.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The guide has no read/write column; access is inferred from its tags (Status = read-only; Cfg, User and Cmd = writable).",
  "The four binary outputs are printed as AO 3-AO 6 (named BO_1-BO_4); AO 4 is printed as \"A04\".",
  "Some MSV state lists are printed in short form (for example \"AI-1, AI-2, AI-3 or AI-4\"); those are kept as printed rather than numbered.",
  "BV 3 OccSched is tagged \"Clg\" in the guide (likely Cfg); treated as writable.",
  "PID loop objects LOOP0-LOOP9 are listed as LO with their printed action and default gains.",
  "Temperature units are listed as °F; the guide prints °F and °C ranges and the controller can be set to metric."
 ],
 "source": {
  "title": "BZ424-LX Configurable VAV MS/TP - Installation and Wiring Guide",
  "doc_number": null,
  "revision_date": null,
  "url": "https://www.cochranesupply.com/media/assets/product/documents/Lynxspring/BZ424%20Installation%20and%20Wiring%20Guide.pdf",
  "unofficial": true,
  "host": "Cochrane Supply"
 },
 "integration": {
  "summary": "Set the address and baud on the DIP switches, configure box type, airflow limits, inputs and auxiliary outputs, then drive occupancy with BV 3 and set the occupied setpoints. Read room temperature, airflow, damper position, occupancy mode and the condensation status.",
  "minimum_points": [
   {
    "ref": "BV 3",
    "name": "OccSched",
    "why": "Occupancy schedule (Day = occupied)"
   },
   {
    "ref": "AV 12",
    "name": "RTSPclg_Occ",
    "why": "Occupied cooling setpoint"
   },
   {
    "ref": "AV 13",
    "name": "RTSPhtg_Occ",
    "why": "Occupied heating setpoint"
   },
   {
    "ref": "MV 24",
    "name": "OccMode",
    "why": "Occupancy mode"
   },
   {
    "ref": "AV 41",
    "name": "RoomT",
    "why": "Room temperature"
   },
   {
    "ref": "AI 4",
    "name": "zAirFlow",
    "why": "Measured airflow"
   },
   {
    "ref": "AV 2",
    "name": "zActiveFlowSP",
    "why": "Active airflow setpoint"
   },
   {
    "ref": "AO 2",
    "name": "zActMod",
    "why": "Damper position, %"
   },
   {
    "ref": "BV 5",
    "name": "Cond_Status",
    "why": "Condensation detected"
   },
   {
    "ref": "AV 39",
    "name": "ValidationErr",
    "why": "Configuration error code (0 = none)"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "MS/TP address is set on DIP switch bank DS2 (1-127); baud on DS1: 010 = 9600, 110 = 19200, 001 = 38400, 011 = 76800.",
   "An EOL jumper terminates the MS/TP trunk on the last controller; a second jumper terminates the TZ sensor bus.",
   "Firmware updates use a USB-COM adapter or a USB to MS/TP converter cable."
  ],
  "gotchas": [
   "K-factor (AV 30) and duct area (AV 31) must match the box for airflow to read right.",
   "BV 10 saves objects to flash and restarts the controller; do not write it cyclically."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "AI_1",
   "description": "Analog input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "AI_2",
   "description": "Analog input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "AI_3",
   "description": "Analog input 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "AI_4",
   "description": "Analog input 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "zAirFlow",
   "description": "Air flow sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "AO_1",
   "description": "Analog output 1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 1,
   "name": "AO_2",
   "description": "Analog output 2",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 2,
   "name": "zActMod",
   "description": "Damper Actuator (modulating)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 3,
   "name": "BO_1",
   "description": "Binary output 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 4,
   "name": "BO_2",
   "description": "Binary output 2",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AO",
   "instance": 5,
   "name": "BO_3",
   "description": "Binary output 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 6,
   "name": "BO_4",
   "description": "Binary output 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "zRunTime",
   "description": "Running time of the actuator(floating)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "zDeadband",
   "description": "Deadbandof the actuator",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "zActiveFlowSP",
   "description": "Active flow setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "MaxAFpos",
   "description": "Maximum airflow (or position)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "MinAFpos",
   "description": "Minmum airflow (or position)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "MinAFpos_Htg",
   "description": "Min. AF (or position) @ 100% heating",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "MinAFpos_Clg",
   "description": "Min. AF (or position) @ 100% cooling",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "RTSPmin_Occ",
   "description": "Minimum Room temp. setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "RTSPmax_Occ",
   "description": "Maximum Room temp. setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "RTSPclg_Occ",
   "description": "Room temp. cooling setpoint, occupied",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "RTSPhtg_Occ",
   "description": "Room temp. heating setpoint, occupied",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "RTSP_DeadBand",
   "description": "RTSPdeadbandbetween Clg and Htg",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "RTSPclg_Unocc",
   "description": "Room temp. cooling setpoint, unoccupied",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "RTSPhtg_Unocc",
   "description": "Room temp. heating setpoint, unoccupied",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "RTSPclg_STBdt",
   "description": "Standby mode, RTSP clg offset (pos.)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "RTSPhtg_STBdt",
   "description": "Standby mode, RTSPhtg offset (neg.)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "ActiveRTSP_Clg",
   "description": "Active cooling room temp. setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "ActiveRTSP_Htg",
   "description": "Active heating room temp. setpoint",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "DSHL_SP",
   "description": "Downstream high limit setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "DSLL_SP",
   "description": "Downstream low limit setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "ChOver_SP",
   "description": "ChOver temp. SP (constant or RoomT+X)",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Calib_RoomT",
   "description": "Room temp. calibration",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Calib_RoomSP",
   "description": "Room temp. Setpoint calibration",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "Calib_usT",
   "description": "Upstream temp. calibration",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "Calib_dsT",
   "description": "Downstream temp. calibration",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "K_Factor",
   "description": "Constantfrom Pitot characteristics",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "DuctArea",
   "description": "Duct area",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "MinOffTime_Htg",
   "description": "Minimum OFF time, heating (BO)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "MinOffTime_Clg",
   "description": "Minimum OFF time, cooling (BO)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "MotionTime",
   "description": "Motion sensor active time",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "OvrTime",
   "description": "Occupancyoverride active time",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "MaxPower",
   "description": "Maximum power allowed",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "OvrRemainTime",
   "description": "Override remaining time",
   "units": "s",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "ValidationErr",
   "description": "0 = no error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "RoomT",
   "description": "Room Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "RoomSP",
   "description": "Room Temperature Setpoint",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "USsupplyT",
   "description": "Upstream supply temp. (from main fan)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "DSsupplyT",
   "description": "Downstream supply temp. (after reheat)",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "AuxA_Out",
   "description": "Auxiliary output A",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "AuxB_Out",
   "description": "Auxiliary output B",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "AuxC_Out",
   "description": "Auxiliary output C",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "AuxD_Out",
   "description": "Auxiliary output D, (Tzone #2)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "AuxE_Out",
   "description": "Auxiliary output E, (Tzone #3)",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "EncodedVal1",
   "description": "Internal Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "EncodedVal2",
   "description": "Internal Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "ActiveTz2SPHtg",
   "description": "Active heating Tzone #2 setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "ActiveTz2SPClg",
   "description": "Active cooling Tzone #2 setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "ActiveTz3SPHtg",
   "description": "Active heating Tzone #3 setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "ActiveTz3SPClg",
   "description": "Active cooling Tzone #3 setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "RoomRH",
   "description": "Room relative humidity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "RoomCO2",
   "description": "Room carbin dioxide (CO2)",
   "units": "ppm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "RoomCO2SP",
   "description": "Room CO2 Setpoint",
   "units": "ppm",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "RoomCO2Dem",
   "description": "Room CO2 demand",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "DewPtHL",
   "description": "Dewpoint Temperature High Limit",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "DewPtLL",
   "description": "Dewpoint Temperature Low Limit",
   "units": "°F",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "DewPoint",
   "description": "Dewpoint Calculated Temperature",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "DewPtOffset",
   "description": "Dewpoint Offset to close cooling valve",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "Chillwater",
   "description": "Chilled Water Reading",
   "units": "°F",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "ActRotation",
   "description": "Actuatorrotation direction",
   "units": "",
   "access": "W",
   "states": "0=Direct, 1=Reverse"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "FanStatus",
   "description": "FanStatus",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "DewPtHL",
   "description": "Dewpoint Temperature High Limit",
   "units": "",
   "access": "W",
   "states": "0=32°F (0°C), 1=122°F (50°C)"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "OccSched",
   "description": "Occupancy schedule",
   "units": "",
   "access": "W",
   "states": "0=Night, 1=Day"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "OvrStatus",
   "description": "Occupancyoverride status",
   "units": "",
   "access": "R",
   "states": "0=Inactive, 1=Active"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Cond_Status",
   "description": "Condensation Status from input",
   "units": "",
   "access": "R",
   "states": "0=Normal, 1=Detected"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "SaveAndRestart",
   "description": "Saves Objects to Flash and restart",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Units_Type",
   "description": "Units configuration (temp. & Airflow)",
   "units": "",
   "access": "W",
   "states": "1=°F, CFM, 2=°C, CFM, 3=°F, LS, 4=°C, LS"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Tstor10K_Type",
   "description": "Thermistors type (std type 3 or type 2)",
   "units": "",
   "access": "W",
   "states": "1=Type 3 (std), 2=Type 2"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "AuxA_Loc",
   "description": "Auxiliary output A physical location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=BO-3, 7=BO-4, 8=Float BO-1,2"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "AuxA_Type",
   "description": "Auxiliary output A control type",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "AuxA_Formula",
   "description": "Auxiliary output A formula",
   "units": "",
   "access": "W",
   "states": "1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev."
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "AuxA_Auto",
   "description": "Auxiliary output A authorization",
   "units": "",
   "access": "W",
   "states": "1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "AuxB_Loc",
   "description": "Auxiliary output B physical location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=BO-3, 7=BO-4, 8=Float BO-1,2"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "AuxB_Type",
   "description": "Auxiliary output B control type",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "AuxB_Formula",
   "description": "Auxiliary output B formula",
   "units": "",
   "access": "W",
   "states": "1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev."
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "AuxB_Auto",
   "description": "Auxiliary output B authorization",
   "units": "",
   "access": "W",
   "states": "1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "AuxC_Loc",
   "description": "Auxiliary output C physical location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=BO-3, 7=BO-4, 8=Float BO-1,2"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "AuxC_Type",
   "description": "Auxiliary output C control type",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool, 8=Parallel Fan, 9=Series Fan"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "AuxC_Formula",
   "description": "Auxiliary output C formula",
   "units": "",
   "access": "W",
   "states": "1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev."
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "AuxC_Auto",
   "description": "Auxiliary output C authorization",
   "units": "",
   "access": "W",
   "states": "1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "RoomT_Loc",
   "description": "Room temp.physical location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AI-1, 3=AI-2, 4=AI-3, 5=AI-4, 6=Tzone, 7=External, 8=AI-1 (Trane), 9=AI-2 (Trane)"
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "RoomSP_Loc",
   "description": "Room setpoint location (occupied)",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AI-1, 3=AI-2, 4=AI-3, 5=AI-4, 6=Tzone, 7=External, 8=AI-1 (Trane), 9=AI-2 (Trane)"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "USsupplyT_Loc",
   "description": "Upstream supply temp. loc. (from main fan)",
   "units": "",
   "access": "W",
   "states": "As printed: None; AI-1, AI-2, AI-3 or AI-4; External"
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "DSsupplyT_Loc",
   "description": "Downstream supply temp. loc (after reheat)",
   "units": "",
   "access": "W",
   "states": "As printed: None; AI-1, AI-2, AI-3 or AI-4"
  },
  {
   "type": "MV",
   "instance": 21,
   "name": "FanStatus_Loc",
   "description": "Fan status location",
   "units": "",
   "access": "W",
   "states": "As printed: None; AI-1(BI), AI-2(BI), AI-3(BI) or AI-1(BI); External"
  },
  {
   "type": "MV",
   "instance": 22,
   "name": "Motion_Loc",
   "description": "Motion sensor location",
   "units": "",
   "access": "W",
   "states": "As printed: None; NO, AI-1 (BI) / NC, AI-1 (BI) / NO, AI-2 (BI) / NC, AI-2 (BI); NO, AI-3 (BI) / NC, AI-3 (BI) / NO, AI-4 (BI) / NC, AI-4 (BI); External"
  },
  {
   "type": "MV",
   "instance": 23,
   "name": "Sched_Loc",
   "description": "Scheduler location",
   "units": "",
   "access": "W",
   "states": "As printed: None; AI-1(BI), AI-2(BI), AI-3(BI) or AI-4(BI); External"
  },
  {
   "type": "MV",
   "instance": 24,
   "name": "OccMode",
   "description": "Occupancy mode",
   "units": "",
   "access": "R",
   "states": "1=Unoccupied, 2=Occupied, 3=Standby"
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "ChOver_Type",
   "description": "Changeover type",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Constant, 3=RoomT°+Offset"
  },
  {
   "type": "MV",
   "instance": 26,
   "name": "HtgClgMode",
   "description": "Heating/cooling mode",
   "units": "",
   "access": "W",
   "states": "1=Heat, 2=Cool, 3=Unused"
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "VAV_Type",
   "description": "VAV box type (dependent/independent)",
   "units": "",
   "access": "W",
   "states": "1=Dependent, 2=Independent, 3=Unused"
  },
  {
   "type": "MV",
   "instance": 29,
   "name": "CoolingWeight",
   "description": "Cooling Weight in demand calculation",
   "units": "",
   "access": "W",
   "states": "1=0 to 10"
  },
  {
   "type": "MV",
   "instance": 30,
   "name": "HeatingWeight",
   "description": "Heating Weight in demand calculation",
   "units": "",
   "access": "W",
   "states": "1=0 to 10"
  },
  {
   "type": "MV",
   "instance": 34,
   "name": "TzControlMode",
   "description": "Control mode with multiple Tzone",
   "units": "",
   "access": "W",
   "states": "1=Tzone1, 2=Tzone2, 3=Tzone3, 4=Average, 5=Maximum Htg., 6=Maximum Clg."
  },
  {
   "type": "MV",
   "instance": 35,
   "name": "AuxD_Loc",
   "description": "Auxiliary output D physical location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=BO-3, 7=BO-4, 8=Float BO-1,2"
  },
  {
   "type": "MV",
   "instance": 36,
   "name": "AuxD_Type",
   "description": "Auxiliary output D control type",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool"
  },
  {
   "type": "MV",
   "instance": 37,
   "name": "AuxD_Formula",
   "description": "Auxiliary output D formula",
   "units": "",
   "access": "W",
   "states": "1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev."
  },
  {
   "type": "MV",
   "instance": 38,
   "name": "AuxD_Auto",
   "description": "Auxiliary output D authorization",
   "units": "",
   "access": "W",
   "states": "1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr"
  },
  {
   "type": "MV",
   "instance": 39,
   "name": "AuxE_Loc",
   "description": "Auxiliary output Ephysical location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AO-1, 3=AO-2, 4=BO-1, 5=BO-2, 6=BO-3, 7=BO-4, 8=Float BO-1,2"
  },
  {
   "type": "MV",
   "instance": 40,
   "name": "AuxE_Type",
   "description": "Auxiliary output Econtrol type",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Elect. Reheat, 3=Water Reheat, 4=Elect. Bboard, 5=Water Bboard, 6=DX Cool, 7=Water Cool"
  },
  {
   "type": "MV",
   "instance": 41,
   "name": "AuxE_Formula",
   "description": "Auxiliary output Eformula",
   "units": "",
   "access": "W",
   "states": "1=0-10 VDC, Dir., 2=0-10 VDC, Rev., 3=2-10 VDC, Dir., 4=2-10 VDC, Rev, 5=On-Off, 6=Pulse, Dir., 7=Pulse, Rev."
  },
  {
   "type": "MV",
   "instance": 42,
   "name": "AuxE_Auto",
   "description": "Auxiliary output E authorization",
   "units": "",
   "access": "W",
   "states": "1=Never, 2=Always, 3=FanStatus, 4=MaxPower, 5=Fan+MaxPwr"
  },
  {
   "type": "MV",
   "instance": 43,
   "name": "Cond_Loc",
   "description": "Condensation detection input Location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AI-1, 3=AI-2, 4=AI-3, 5=AI-4"
  },
  {
   "type": "MV",
   "instance": 62,
   "name": "RoomTSPType",
   "description": "Room Temp Setpoint Type(in Occupied)",
   "units": "",
   "access": "W",
   "states": "1=Heating, 2=Central, 3=Cooling"
  },
  {
   "type": "MV",
   "instance": 70,
   "name": "ChillWaterLoc",
   "description": "Chill Water Input Location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=AI-1, 3=AI-2, 4=AI-3, 5=AI-4, 6=External"
  },
  {
   "type": "MV",
   "instance": 71,
   "name": "HumLoc",
   "description": "Humidity reading Location",
   "units": "",
   "access": "W",
   "states": "1=None, 2=Tzone(s), 3=External"
  },
  {
   "type": "MV",
   "instance": 72,
   "name": "TimedOvrStatus",
   "description": "Timed Override Status",
   "units": "",
   "access": "R",
   "states": "1=Idle, 2=TimedOvrRequest, 3=TimedOvrCancel"
  },
  {
   "type": "LO",
   "instance": 0,
   "name": "zPidFlow",
   "description": "Flow control PID loop (Reverse acting, Kp 0.3, Ki 0.01, bias 50)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 1,
   "name": "PidRoomT_Clg",
   "description": "Room temp. control loop, cooling (Direct acting, Kp 20, Ki 0.05, bias 0)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 2,
   "name": "PidRoomT_Htg",
   "description": "Room temp. control loop, heating (Reverse acting, Kp 20, Ki 0.05, bias 0)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 3,
   "name": "PidHL_DST",
   "description": "Downstream high limit control loop (Reverse acting, Kp 5, Ki 0.1, bias 50)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 4,
   "name": "PidLL_DST",
   "description": "Downstream low limit control loop (Direct acting, Kp 5, Ki 0.1, bias 50)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 6,
   "name": "PidRoomTz2_Clg",
   "description": "Room temp. control loop, cooling (Direct acting, Kp 20, Ki 0.05, bias 0)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 7,
   "name": "PidRoomTz2_Htg",
   "description": "Room temp. control loop, heating (Reverse acting, Kp 20, Ki 0.05, bias 0)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 8,
   "name": "PidRoomTz3_Clg",
   "description": "Room temp. control loop, cooling (Direct acting, Kp 20, Ki 0.05, bias 0)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 9,
   "name": "PidRoomTz3_Htg",
   "description": "Room temp. control loop, heating (Reverse acting, Kp 20, Ki 0.05, bias 0)",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/lynxspring/bz424-lx",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}