 "manufacturer": "Functional Devices",
 "manufacturer_slug": "functional-devices",
 "model": "RIBTWX240xB-BC / RIBMNWX240xB-BC BACnet relay (1 relay, 2 inputs)",
 "model_slug": "ribxw240xb-bc",
 "aliases": [
  "RIBTWX240xB-BC",
  "RIBMNWX240xB-BC",
  "RIBxW240xB-BC",
  "RIBTWX2401B-BC",
  "BACnet RIB relay 2 inputs"
 ],
 "equipment_type": "Other equipment (BACnet relay / I/O module)",
 "applies_to": "Functional Devices RIBTWX240xB-BC (enclosed) and RIBMNWX240xB-BC (board) BACnet MS/TP relays with one relay output and two binary inputs.",
 "summary": "A BACnet MS/TP relay with one relay (BO1) and two binary inputs (BI1, BI2). All three objects are plain I/O with user-writable names; there is no on-board control logic.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "Firmware 2.04, application 1.1",
 "default_device_instance": 277000,
 "access_inferred": false,
 "notes": [
  "Object names are user-writable and the PICS prints no factory default name, so each object is listed by its printed ID (BI1, BO1...).",
  "BO1 has a 16-level priority array and writable minimum on / off times (0-65535 s); polarity and active / inactive texts are writable on every object.",
  "The PICS lists AnalogInput among the supported object types, but the object list has only BI1, BI2 and BO1."
 ],
 "source": {
  "title": "RIBxW240xB-BC PICS v1.1",
  "doc_number": null,
  "revision_date": "2016-06-24",
  "url": "https://www.functionaldevices.com/sfsites/c/cms/delivery/media/MCAB425QWSPFEJ5NM76IFS54YAME"
 },
 "integration": {
  "summary": "Write BO1 to switch the relay and read BI1 and BI2 for the inputs.",
  "minimum_points": [
   {
    "ref": "BO 1",
    "why": "Relay command",
    "name": "BO1"
   },
   {
    "ref": "BI 1",
    "why": "Binary input 1 status",
    "name": "BI1"
   },
   {
    "ref": "BI 2",
    "why": "Binary input 2 status",
    "name": "BI2"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "The PICS prints the device object ID default as DE277000 (vendor ID 277); it is writable.",
   "MS/TP master; the PICS lists 9600-115200 baud. Max_Master defaults to 127."
  ],
  "gotchas": []
 },
 "points": [
  {
   "type": "BI",
   "instance": 1,
   "name": "BI1",
   "description": "Binary input 1 status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "BI2",
   "description": "Binary input 2 status",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BO",
   "instance": 1,
   "name": "BO1",
   "description": "Relay command",
   "units": "",
   "access": "C",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/functional-devices/ribxw240xb-bc",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}