 "manufacturer": "Fox Thermal",
 "manufacturer_slug": "fox-thermal",
 "model": "FT1 thermal mass flow meter, BACnet MS/TP",
 "model_slug": "ft1-thermal-mass-flow-meter",
 "aliases": [
  "FT1",
  "Fox Thermal FT1",
  "Model FT1",
  "ONICON F-5500",
  "F-5500",
  "F-5500 thermal mass flow sensor"
 ],
 "equipment_type": "Gas flow meter (thermal mass)",
 "applies_to": "Fox Thermal FT1 gas thermal mass flow meters with the RS485 BACnet MS/TP option; the ONICON F-5500 manual prints the same four objects.",
 "summary": "The FT1 is an insertion or inline thermal mass flow meter for gases. With the RS485 option set to BACnet MS/TP it acts as a BACnet Smart Sensor with four Analog Inputs: flow, gas temperature, flow total and elapsed time since the total was reset.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": null,
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The manual lists the objects as plain text (Analog Input 1 = Flow and so on) without units or access; all four are listed read-only here and units follow the meter's display settings.",
  "The ONICON F-5500 thermal mass flow sensor manual (DOC-0005059) prints the identical four objects; that meter reports ONICON's vendor ID 206 instead of Fox Thermal's 650.",
  "The AI 3 label \"Total Flow / Reset Total\" suggests the total can be reset, but the manual does not say how to do it over BACnet; the front-panel reset is described."
 ],
 "source": {
  "title": "Model FT1 Fox Thermal Gas Mass Flow Meter - Instruction Manual",
  "doc_number": "Document #106012 Rev M",
  "revision_date": null,
  "url": "https://www.foxthermal.com/products/pdf/ft1/ft1-manual.pdf"
 },
 "integration": {
  "summary": "Choose BACnet in the COM menu, set baud, MAC, Max Master, device instance and name, power cycle, then read AI 1 flow and AI 3 total.",
  "minimum_points": [
   {
    "ref": "AI 1",
    "name": "Flow",
    "why": "Gas flow rate"
   },
   {
    "ref": "AI 3",
    "name": "Total Flow / Reset Total",
    "why": "Flow total since last reset"
   },
   {
    "ref": "AI 2",
    "name": "Gas Temperature",
    "why": "Gas temperature"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "In I/O > COM set Comm=BACnet, then baud (9600-115200), MAC (0-127), Max Master, device instance (0-4194303) and device name (9 characters max).",
   "A power cycle is needed before new communication settings take effect.",
   "Device profile is BACnet Smart Sensor (B-SS); Fox Thermal vendor ID 650."
  ],
  "gotchas": [
   "Modbus RTU and BACnet MS/TP are only available if the RS485 option was ordered from the factory."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 1,
   "name": "Flow",
   "description": "Gas mass flow rate",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "Gas Temperature",
   "description": "Gas temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "Total Flow / Reset Total",
   "description": "Flow total since last reset",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "Elapsed Time since reset",
   "description": "Time since the total was reset",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/fox-thermal/ft1-thermal-mass-flow-meter",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}