 "manufacturer": "Daikin Applied",
 "manufacturer_slug": "daikin-applied",
 "model": "EWWT-Q / EWLT-Q / EWHT-Q water-cooled scroll chiller (Daikin Applied Europe)",
 "model_slug": "ewwt-q-ewlt-q-ewht-q-bacnet",
 "short_model": "EWWT-Q / EWLT-Q / EWHT-Q",
 "aliases": [
  "EWWT-Q",
  "EWLT-Q",
  "EWHT-Q",
  "EWWTQ",
  "PROXIMA",
  "D-EIGOC00106",
  "WCZ"
 ],
 "equipment_type": "Water-cooled scroll chiller controller",
 "applies_to": "Daikin Applied Europe EWWT-Q water-cooled scroll chillers, EWLT-Q condenserless units and EWHT-Q water-to-water heat pumps with the PROXIMA software (POL486.65 controller), including MUSE multi-unit groups of up to 4 units.",
 "summary": "The EWWT-Q, EWLT-Q and EWHT-Q units run Daikin's PROXIMA software on a POL486.65 controller. BACnet IP is a software option on the Ethernet port, enabled with connectivity kit EKRSCBMS. The list covers unit enable, network mode and cool/heat setpoints, water temperatures, pump status, one refrigerant circuit with two compressors, bit-coded unit and circuit alarm words, and MUSE master/slave data for up to four units.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "PROXIMA",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "This is the Daikin Applied Europe guide; it is a different object list from the US MicroTech chiller documents.",
  "Unit and circuit alarms are packed into 32-bit alarm words (AV 296-299, AV 396-399); the bit meanings are in Annex A of the guide.",
  "AV 151 MUSECtrlTemp is printed twice (once read-only, once writable as the MUSE temperature setpoint); it is listed once as W.",
  "BV 502 is printed twice (CommonLWTSenf and CmnLwtSenf) and BV 503 twice (CndLvgTempSensorFail and CommonCondLWTSenf); each is listed once under its first name, with the other name in the description.",
  "MU2-MU4 and MUSE objects only apply to multi-unit (MUSE) installations.",
  "Units shown are metric as printed; MV 47 Units switches the BACnet values between Imperial and Metric."
 ],
 "source": {
  "title": "BAS Integration guide - BACnet protocol (EWWT-Q/EWLT-Q/EWHT-Q)",
  "doc_number": "D-EIGOC00106-24_02EN_WCZ",
  "revision_date": "2024",
  "url": "https://www.daikinapplied.eu/hubfs/portale-documentale/D_EIGOC00106_24_02EN_WCZ.pdf"
 },
 "integration": {
  "summary": "Select network control at the unit (ChillerLocalRemote BI 3 then reads Network), enable the chiller with ChillerEnableStp and write the network mode and cool/heat setpoints. Monitor unit status, leaving water temperature, the general alarm output and the alarm words.",
  "minimum_points": [
   {
    "ref": "BV 2",
    "name": "ChillerEnableStp",
    "why": "Network enable/disable of the chiller"
   },
   {
    "ref": "MV 3",
    "name": "ChillerOperationMode",
    "why": "Ice / cool / heat mode command"
   },
   {
    "ref": "AV 4",
    "name": "NetworkCoolTempSetpoint",
    "why": "Leaving water cool setpoint from the BMS"
   },
   {
    "ref": "AV 6",
    "name": "NetworkHeatTempSetpoint",
    "why": "Leaving water heat setpoint from the BMS"
   },
   {
    "ref": "BV 8",
    "name": "ClearAlarm",
    "why": "Clear alarms from the network"
   },
   {
    "ref": "BI 3",
    "name": "ChillerLocalRemote",
    "why": "Shows whether network control is active"
   },
   {
    "ref": "MV 1",
    "name": "UnitStatus",
    "why": "Unit run state"
   },
   {
    "ref": "AI 2",
    "name": "LvgEvapWaterTempUnit",
    "why": "Leaving evaporator water temperature"
   },
   {
    "ref": "BI 10",
    "name": "AlarmDigitalOutput",
    "why": "Any active alarm"
   },
   {
    "ref": "AV 299",
    "name": "UnitAlarmsWord1",
    "why": "Unit alarm word 1 (bits per Annex A)"
   }
  ],
  "enable": "ChillerLocalRemote (BI 3) reads 0 = Network / 1 = Local and is read-only over BACnet, so network control has to be selected at the unit; the guide does not describe that step. With network control active the BMS writes ChillerEnableStp (BV 2) = Enable, then the mode (MV 3) and network setpoints.",
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet IP runs on the controller's Ethernet port as a software option, supplied with connectivity kit EKRSCBMS.",
   "The onboard RS485 port is for Modbus; this guide does not cover BACnet MS/TP."
  ],
  "gotchas": [
   "Compressor and pump run-hour AVs are marked writable; don't write them from the BMS.",
   "Alarms are bit-coded in the unit and circuit alarm words; decode them with Annex A.",
   "MV 47 Units switches metric/imperial for the BACnet values; set it once, not cyclically.",
   "MV 430/435 set each compressor to Off or Auto; leave them on Auto for normal running."
  ]
 },
 "points": [
  {
   "type": "BI",
   "instance": 3,
   "name": "ChillerLocalRemote",
   "description": "Unit Local/Remote",
   "units": "",
   "access": "R",
   "states": "0=Network, 1=Local"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "ChillerEnableOutput",
   "description": "Unit Enable Output",
   "units": "",
   "access": "R",
   "states": "0=Disabled, 1=Enabled"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "AlarmDigitalOutput",
   "description": "Unit general alarm",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "ChillerEnableStp",
   "description": "Unit Enable Setpoint",
   "units": "",
   "access": "W",
   "states": "0=Disable, 1=Enable"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "ClearAlarm",
   "description": "Clear Alarms - Network",
   "units": "",
   "access": "W",
   "states": "0=None, 1=ClearAlarm"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Active Mode",
   "description": "Unit Mode Output",
   "units": "",
   "access": "R",
   "states": "0=Ice, 1=Cool, 2=Heat, 3=Test"
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "ActiveLvgWaterTarget",
   "description": "Active Setpoint",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "ChillerCapacity",
   "description": "Actual Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "ActiveCapacityLimit",
   "description": "Active Capacity Limit Output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "EntEvapWaterTemp",
   "description": "Evaporator Entering Water Temp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "LvgEvapWaterTempUnit",
   "description": "Evaporator Leaving Water Temp Unit",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 748,
   "name": "EvapLvgWTempSen",
   "description": "Evaporator LWT sensor fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 501,
   "name": "EvapEntWTempSensorFail",
   "description": "Evaporator EWT sensor fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "MV",
   "instance": 701,
   "name": "UnitOFFEvapWaterFlow",
   "description": "Unit Off Evaporator Water Flow",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 11,
   "name": "EvapWaterFlowStatus",
   "description": "Evaporator Flow Switch Input State",
   "units": "",
   "access": "R",
   "states": "0=NoFlow, 1=Flow"
  },
  {
   "type": "BV",
   "instance": 702,
   "name": "EvapLvgWTempLo",
   "description": "Evaporator Water Freeze Alarm",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "AV",
   "instance": 296,
   "name": "UnitAlarmsWord4",
   "description": "Unit Alarm Word #4 (bit-coded, see Annex A)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 297,
   "name": "UnitAlarmsWord3",
   "description": "Unit Alarm Word #3 (bit-coded, see Annex A)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 298,
   "name": "UnitAlarmsWord2",
   "description": "Unit Alarm Word #2 (bit-coded, see Annex A)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 299,
   "name": "UnitAlarmsWord1",
   "description": "Unit Alarm Word #1 (bit-coded, see Annex A)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 151,
   "name": "MUSECtrlTemp",
   "description": "MUSE control temperature setpoint",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 513,
   "name": "BadDemandLimitInput",
   "description": "Demand Limit Input Fail",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 512,
   "name": "BadSPointOverrideInput",
   "description": "Setpoint Override Input Fail",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "CondFlowSwitchStatus",
   "description": "Condenser Flow Switch Input State",
   "units": "",
   "access": "R",
   "states": "0=NoFlow, 1=Flow"
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "EntCondWaterTemp",
   "description": "Condenser EWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 500,
   "name": "CndEntWTempSensorFail",
   "description": "Condenser EWT sensor fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "LvgCondWaterTempUnit",
   "description": "Condenser LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 503,
   "name": "CndLvgTempSensorFail",
   "description": "Condenser LWT sensor fault; also printed as CommonCondLWTSenf",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "ChillerOperationMode",
   "description": "Unit Mode Setpoint - Network",
   "units": "",
   "access": "W",
   "states": "0=Null, 1=Ice, 2=Cool, 3=Heat"
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "NetworkCoolTempSetpoint",
   "description": "Cool Setpoint - Network",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "NetworkHeatTempSetpoint",
   "description": "Heat Setpoint - Network",
   "units": "°C",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 47,
   "name": "Units",
   "description": "Measure Units",
   "units": "",
   "access": "W",
   "states": "1=Imperial, 2=Metric"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "EvapPump1State",
   "description": "Evaporator Pump #1 Status",
   "units": "",
   "access": "R",
   "states": "0=OffRequest, 1=OnRequest"
  },
  {
   "type": "BV",
   "instance": 575,
   "name": "EvPumpFault1",
   "description": "Evaporator Pump #1 Fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "EvapPump1OperHours",
   "description": "Evaporator Pump #1 Run Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 121,
   "name": "CondPump1State",
   "description": "Condenser Pump #1 Status",
   "units": "",
   "access": "R",
   "states": "0=OffRequest, 1=OnRequest"
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "CondPump1OperHours",
   "description": "Condenser Pump #1 Run Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 120,
   "name": "CondPump1Fault",
   "description": "Condenser Pump #1 Fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 923,
   "name": "ExternalAlarm",
   "description": "Unit External Alarm",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 924,
   "name": "UnitExternalEvent",
   "description": "Unit External Event",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "MV",
   "instance": 300,
   "name": "C1State",
   "description": "Circuit #1 Status",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Preopen, 3=Start, 4=Run, 5=Pumpdown"
  },
  {
   "type": "AV",
   "instance": 160,
   "name": "ActualCapacityCir1",
   "description": "Circuit #1 - Actual Capacity",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "C1Comp1Hours",
   "description": "Circuit #1 Comp #1 - Run Hours",
   "units": "h",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 430,
   "name": "CompressorOffAutoC1Comp1",
   "description": "Circuit #1 Compressor #1 Auto",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=Auto"
  },
  {
   "type": "BV",
   "instance": 760,
   "name": "C1OFFHighPress",
   "description": "Circuit #1 Alarm",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 431,
   "name": "CompressorStatusC1Comp1",
   "description": "Circuit #1 Compressor #1 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "AI",
   "instance": 105,
   "name": "C1SuctionTemp",
   "description": "Circuit #1 Suction Temp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 857,
   "name": "C1OFFSuctTempSen",
   "description": "Circuit #1 Suction Temp Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "MV",
   "instance": 435,
   "name": "CompressorOffAutoC1Comp2",
   "description": "Circuit #1 Compressor #2 Auto",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=Auto"
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "C1Comp2Hours",
   "description": "Circuit #1 Compressor #2 Run hours",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 436,
   "name": "CompressorStatusC1Comp2",
   "description": "Circuit #1 Compressor #2 Status",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BV",
   "instance": 668,
   "name": "C1OFFCondPressSen",
   "description": "Circuit #1 Condenser pressure sensor fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "AI",
   "instance": 99,
   "name": "Cond1RefPressure",
   "description": "Circuit #1 Condenser pressure",
   "units": "kPa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "Cond1SatRefTemp",
   "description": "Circuit #1 Condenser saturated refrigerant Temp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 168,
   "name": "Evap1EXVPositionCir1",
   "description": "Circuit #1 EXV Position",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 711,
   "name": "C1OFFEvapPressSen",
   "description": "Circuit #1 Evaporator pressure sensor fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "AI",
   "instance": 141,
   "name": "C1EvapRefPressure",
   "description": "Circuit #1 Evaporator pressure",
   "units": "kPa",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "C1EvapSatRefTemp",
   "description": "Circuit #1 Evaporator saturated refrigerant Temp",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 676,
   "name": "C1OFFCondPressHi",
   "description": "Circuit #1 High Condenser Pressure",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 704,
   "name": "C1OFFEvapPressLow",
   "description": "Circuit #1 Low Evaporator pressure",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 905,
   "name": "C1CompNoPressChStart",
   "description": "Circuit #1 No pressure change at start fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "AV",
   "instance": 169,
   "name": "OutdoorFanSpeedCir1",
   "description": "Circuit #1 VFD Speed",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 516,
   "name": "C1FailedPumpdown",
   "description": "Circuit #1 Pumpdown failed",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "AV",
   "instance": 396,
   "name": "C1AlarmWord4",
   "description": "Circuit #1 Alarm Word #4 (bit-coded, see Annex A)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 397,
   "name": "C1AlarmWord3",
   "description": "Circuit #1 Alarm Word #3 (bit-coded, see Annex A)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 398,
   "name": "C1AlarmWord2",
   "description": "Circuit #1 Alarm Word #2 (bit-coded, see Annex A)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 399,
   "name": "C1AlarmWord1",
   "description": "Circuit #1 Alarm Word #1 (bit-coded, see Annex A)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1135,
   "name": "MUStandalone",
   "description": "MU Standalone",
   "units": "",
   "access": "W",
   "states": "1=No, 2=Yes"
  },
  {
   "type": "BV",
   "instance": 502,
   "name": "CommonLWTSenf",
   "description": "CommonLWT sensor fault; also printed as CmnLwtSenf",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "MasterCommErr",
   "description": "MUSE Comm Err",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "MU2CommErr",
   "description": "MU2 Comm Err",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "MU3CommErr",
   "description": "MU3 Comm Err",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "BV",
   "instance": 1437,
   "name": "MU4CommErr",
   "description": "MU4 Comm Err",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "AV",
   "instance": 1168,
   "name": "MU2Load",
   "description": "MU2 Load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1172,
   "name": "MU2State",
   "description": "MU2 State",
   "units": "",
   "access": "R",
   "states": "0=Stop, 1=Run"
  },
  {
   "type": "AV",
   "instance": 1186,
   "name": "MU3Load",
   "description": "MU3 Load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1190,
   "name": "MU3State",
   "description": "MU3 State",
   "units": "",
   "access": "R",
   "states": "0=Stop, 1=Run"
  },
  {
   "type": "AV",
   "instance": 1204,
   "name": "Slave3Load",
   "description": "MU4 Load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1208,
   "name": "MU4State",
   "description": "MU4 State",
   "units": "",
   "access": "R",
   "states": "0=Stop, 1=Run"
  },
  {
   "type": "MV",
   "instance": 1100,
   "name": "MUSEOpSta",
   "description": "MUSE Operating State",
   "units": "",
   "access": "R",
   "states": "0=Stop, 1=Run"
  },
  {
   "type": "AI",
   "instance": 1103,
   "name": "CmnLwt",
   "description": "Common Evaporator LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1104,
   "name": "CmnCondLwt",
   "description": "Common Condenser LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1433,
   "name": "CmnCondLwtSenf",
   "description": "Common Condenser LWT Sensor Fault",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "MV",
   "instance": 1137,
   "name": "MUSEActMode",
   "description": "MUSE Actual Mode",
   "units": "",
   "access": "R",
   "states": "0=Cool, 1=Ice, 2=Heat, 3=Test, 4=Pursuit"
  },
  {
   "type": "AV",
   "instance": 1112,
   "name": "MUSELoad",
   "description": "MUSE Load",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1324,
   "name": "MU1Enabling",
   "description": "MU1 Enable",
   "units": "",
   "access": "W",
   "states": "0=Enable, 1=Disable"
  },
  {
   "type": "MV",
   "instance": 1526,
   "name": "MUSEClrTmr",
   "description": "MUSE Clear Timers",
   "units": "",
   "access": "W",
   "states": "0=Off, 1=Reset"
  },
  {
   "type": "BV",
   "instance": 1390,
   "name": "PumpSkidComEr",
   "description": "PumpSkid Communication Error",
   "units": "",
   "access": "R",
   "states": "0=NoAlarm, 1=Alarm"
  },
  {
   "type": "MV",
   "instance": 1155,
   "name": "MU2ActMode",
   "description": "MU2 Actual Mode",
   "units": "",
   "access": "R",
   "states": "0=Cool, 1=Ice, 2=Heat, 3=Test, 4=Pursuit"
  },
  {
   "type": "AV",
   "instance": 1167,
   "name": "MU2ELWT",
   "description": "MU2 Evaporator LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1166,
   "name": "MU2EEWT",
   "description": "MU2 Evaporator EWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1164,
   "name": "MU2CEWT",
   "description": "MU2 Condenser EWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1165,
   "name": "MU2CLWT",
   "description": "MU2 Condenser LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1173,
   "name": "MU3ActMode",
   "description": "MU3 Actual Mode",
   "units": "",
   "access": "R",
   "states": "0=Cool, 1=Ice, 2=Heat, 3=Test, 4=Pursuit"
  },
  {
   "type": "AV",
   "instance": 1185,
   "name": "MU3ELWT",
   "description": "MU3 Evaporator LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1184,
   "name": "MU3EEWT",
   "description": "MU3 Evaporator EWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1182,
   "name": "MU3CLWT",
   "description": "MU3 Condenser EWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1183,
   "name": "MU3CEWT",
   "description": "MU3 Condenser LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 1191,
   "name": "MU4ActMode",
   "description": "MU4 Actual Mode",
   "units": "",
   "access": "R",
   "states": "0=Cool, 1=Ice, 2=Heat, 3=Test, 4=Pursuit"
  },
  {
   "type": "AV",
   "instance": 1203,
   "name": "MU4ELWT",
   "description": "MU4 Evaporator LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1202,
   "name": "MU4EEWT",
   "description": "MU4 Evaporator EWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1200,
   "name": "MU4CLWT",
   "description": "MU4 Condenser EWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1201,
   "name": "MU4CEWT",
   "description": "MU4 Condenser LWT",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 54,
   "name": "U'ShutdownAlm",
   "description": "Unit - Shutdown Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MV",
   "instance": 51,
   "name": "C1'ShutdownAlm",
   "description": "Compressor 1 - Shutdown Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MV",
   "instance": 52,
   "name": "C2'ShutdownAlm",
   "description": "Compressor 2 - Shutdown Alarm",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "UnitOnOff",
   "description": "UnitOnOff",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=On"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "UnitStatus",
   "description": "UnitStatus",
   "units": "",
   "access": "R",
   "states": "0=Off, 1=Start, 2=Run, 3=Pre Shutdown, 4=Service"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/daikin-applied/ewwt-q-ewlt-q-ewht-q-bacnet",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}