 "manufacturer": "Circutor",
 "manufacturer_slug": "circutor",
 "model": "CVM-C10 / CVM-C11 / CVM-B100 / CVM-B150 / CVM-E3-MINI power analyzers (BACnet)",
 "model_slug": "cvm-c10",
 "aliases": [
  "CVM-C10",
  "CVM-C11",
  "CVM-B100",
  "CVM-B150",
  "CVM-E3-MINI",
  "CVM-C11-ITF-IN-ETH-ICT2",
  "Circutor power analyzer BACnet"
 ],
 "equipment_type": "Power meter (power analyzer)",
 "applies_to": "Circutor CVM-C10, CVM-C11, CVM-B100, CVM-B150 and CVM-E3-MINI panel power analyzers with BACnet communications.",
 "summary": "These Circutor power analyzers share one BACnet object map: 50 Analog Inputs for per-phase and three-phase voltage, current, power, power factor, THD, energy (consumed and generated) and maximum demand, plus three Analog Values for the MS/TP address, baud rate and device instance. They talk BACnet MS/TP over RS-485; the CVM-C11 Ethernet model can run BACnet IP instead.",
 "bacnet_transport": [
  "BACnet MS/TP",
  "BACnet IP"
 ],
 "firmware": "CVM-C10: BACnet available from device version 3.00",
 "default_device_instance": null,
 "access_inferred": true,
 "notes": [
  "The same object table (AI 0-49, AV 1-3) is printed in the CVM-C10 (M001B01-03-23A), CVM-C11 (M361B01-03-25A) and CVM-B100/B150 (M010B01-03-26A) manuals. The CVM-E3-MINI manual (M170B01-03-25B) prints it without AI 39 NeutralCurrent.",
  "BACnet IP is only on the CVM-C11-ITF-IN-ETH-ICT2 Ethernet model (Ethernet protocol set to BACnet IP, UDP 47808); the others are BACnet MS/TP only.",
  "The PICS has no read/write column. AIs are read-only; the manual says the AV address, baud and ID objects can be written.",
  "Object names are kept as printed, including Ph2NU1-3 for the phase-to-neutral voltages and MaxDemand_kVA (printed with a line break after the underscore in some manuals).",
  "Units here are the printed symbols; the manual prints I_AVG and In in the units column for AI 38 and AI 39 (amps)."
 ],
 "source": {
  "title": "CVM-C10 Power analyzer Instruction Manual (section 4.10.5 PICS map)",
  "doc_number": "M001B01-03-23A",
  "revision_date": null,
  "url": "https://docs.circutor.com/docs/M001B01-03.pdf"
 },
 "integration": {
  "summary": "Set the MS/TP MAC, baud and device ID on the meter (or through the AV objects or the device Object_Name commands), then read the power, energy and demand AIs. Nothing needs to be written for normal monitoring.",
  "minimum_points": [
   {
    "ref": "AI 15",
    "name": "ActPwOn3Ph",
    "why": "Three-phase active power, kW"
   },
   {
    "ref": "AI 30",
    "name": "ActEnergy",
    "why": "Active energy consumed, kWh"
   },
   {
    "ref": "AI 0",
    "name": "Ph2NU1",
    "why": "Voltage L1-N"
   },
   {
    "ref": "AI 1",
    "name": "Ph1Current",
    "why": "Current L1"
   },
   {
    "ref": "AI 19",
    "name": "PwFactOn3Ph",
    "why": "Three-phase power factor"
   },
   {
    "ref": "AI 48",
    "name": "MaxDemand_kW",
    "why": "Maximum demand, kW"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "Default MAC 2. Default baud: 9600 (CVM-C10, CVM-C11), 19200 (CVM-E3-MINI), 38400 (CVM-B100/B150).",
   "MAC, baud and ID can also be set by writing '#MAC x', '#Baud x' or '#ID x' to the Device object's Object_Name.",
   "CVM-C11 Ethernet model: choose BACnet IP as the Ethernet protocol; default UDP port 47808."
  ],
  "gotchas": [
   "Energy values are three-phase totals; consumed and generated are separate objects.",
   "Voltage objects are named Ph2NU1-3 for all three phases, not Ph1/Ph2/Ph3."
  ]
 },
 "points": [
  {
   "type": "AI",
   "instance": 0,
   "name": "Ph2NU1",
   "description": "Voltage L1-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "Ph1Current",
   "description": "Current L1",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "ActPwrPh1",
   "description": "Active power L1",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "ReactPwrPh1",
   "description": "Reactive power L1",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "PwrFactPh1",
   "description": "Power factor L1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "Ph2NU2",
   "description": "Voltage L2-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "Ph2Current",
   "description": "Current L2",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "ActPwrPh2",
   "description": "Active power L2",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "ReactPwrPh2",
   "description": "Reactive power L2",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "PwrFactPh2",
   "description": "Power factor L2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "Ph2NU3",
   "description": "Voltage L3-N",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "Ph3Current",
   "description": "Current L3",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "ActPwrPh3",
   "description": "Active power L3",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "ReactPwrPh3",
   "description": "Reactive power L3",
   "units": "kvar",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "PwrFactPh3",
   "description": "Power factor L3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "ActPwOn3Ph",
   "description": "Three-phase active power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "InductPwOn3Ph",
   "description": "Three-phase inductive reactive power",
   "units": "kvarL",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "CapPwOn3Ph",
   "description": "Three-phase capacitive reactive power",
   "units": "kvarC",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "Cosphi",
   "description": "Three-phase cos phi",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "PwFactOn3Ph",
   "description": "Three-phase power factor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "Frequency",
   "description": "Frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "Ph2PhU12",
   "description": "Voltage L1-L2",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "Ph2PhU23",
   "description": "Voltage L2-L3",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "Ph2PhU31",
   "description": "Voltage L3-L1",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "THDVal_U1",
   "description": "Voltage THD L1",
   "units": "%THD",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "THDVal_U2",
   "description": "Voltage THD L2",
   "units": "%THD",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "THDVal_U3",
   "description": "Voltage THD L3",
   "units": "%THD",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "THDVal_I1",
   "description": "Current THD L1",
   "units": "%THD",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "THDVal_I2",
   "description": "Current THD L2",
   "units": "%THD",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "THDVal_I3",
   "description": "Current THD L3",
   "units": "%THD",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "ActEnergy",
   "description": "Three-phase active energy, consumed",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "InductEnergy",
   "description": "Three-phase inductive reactive energy, consumed",
   "units": "kvarLh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "CapEnergy",
   "description": "Three-phase capacitive reactive energy, consumed",
   "units": "kvarCh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "AppEnergy",
   "description": "Three-phase apparent energy, consumed",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "ActEnergy_exp",
   "description": "Three-phase active energy, generated",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "IndEnergy_exp",
   "description": "Three-phase inductive reactive energy, generated",
   "units": "kvarLh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "CapEnergy_exp",
   "description": "Three-phase capacitive reactive energy, generated",
   "units": "kvarCh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "AppEnergy_exp",
   "description": "Three-phase apparent energy, generated",
   "units": "kVAh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "AvgValCurr3Ph",
   "description": "Three-phase average current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "NeutralCurrent",
   "description": "Neutral current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "AppPwrPh1",
   "description": "Apparent power L1",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "AppPwrPh2",
   "description": "Apparent power L2",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "AppPwrPh3",
   "description": "Apparent power L3",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "AppPw3Ph",
   "description": "Three-phase apparent power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "MaxDemand_A1",
   "description": "Maximum demand, current L1",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "MaxDemand_A2",
   "description": "Maximum demand, current L2",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "MaxDemand_A3",
   "description": "Maximum demand, current L3",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "MaxDemand_A",
   "description": "Maximum demand, three-phase current",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "MaxDemand_kW",
   "description": "Maximum demand, active power",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "MaxDemand_kVA",
   "description": "Maximum demand, apparent power",
   "units": "kVA",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "MAC_Address",
   "description": "MS/TP MAC address",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "BaudRate",
   "description": "MS/TP baud rate",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Device_ID",
   "description": "BACnet device instance",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/circutor/cvm-c10",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}