 "manufacturer": "Bosch",
 "manufacturer_slug": "bosch",
 "model": "REGO 5200 heat pump controller (Supraeco T)",
 "model_slug": "rego-5200-heat-pump-controller",
 "aliases": [
  "REGO 5200",
  "REGO5200",
  "Supraeco T",
  "Bosch Supraeco T BACnet",
  "6 720 821 165",
  "Bosch ground source heat pump BACnet"
 ],
 "equipment_type": "Heat pump controller",
 "applies_to": "Bosch REGO 5200 controller used in Bosch Supraeco T ground-source / water heat pumps, program 1.3-0-00 and later.",
 "summary": "The REGO 5200 heat pump controller publishes one BACnet device (instance 2001) with about 250 objects: heat curve and DHW settings, communicated (override) sensor values and setpoints as AVs, sensor readings and run-time meters as AVs, compressor and pump commands/statuses and I/O as BVs, and one Multi-state Value per alarm. The same data is also on Modbus.",
 "bacnet_transport": [],
 "firmware": "Program 1.3-0-00 and later (document 1.3.1-01)",
 "default_device_instance": 2001,
 "access_inferred": false,
 "notes": [
  "The manual does not say which BACnet data link (IP or MS/TP) the controller uses; the Modbus side is Modbus TCP.",
  "Object types are printed as BACnet type numbers (2 = AV, 5 = BV, 19 = MSV).",
  "Access comes from the printed 'settable' column (Y = writable).",
  "Units are not printed; temperatures and setpoints follow the controller's units.",
  "Each alarm (Alarm1-Alarm105) is its own MSV (instances 19-123); alarm numbers are not continuous (e.g. no Alarm92).",
  "Instance gaps (AV 46-63, AV 66, MSV 4-9) are as printed."
 ],
 "source": {
  "title": "Modbus/ Bacnet protocol REGO 5200",
  "doc_number": "6 720 821 165",
  "revision_date": "2016/11",
  "url": "https://www.bosch-homecomfort.com/ocsmedia/optimized/full/o451341v272_Modbus-Protokoll_Supraeco_T-2.pdf"
 },
 "integration": {
  "summary": "Keep the third-party watchdog alive with BV 4, use BV 1-3 to allow or force the compressors, and write the communicated flow setpoint or sensor values when override mode is used. Read sensor values, compressor run states and the summary alarms.",
  "minimum_points": [
   {
    "ref": "BV 1",
    "name": "externalCompressorStartEnable",
    "why": "Third-party compressor start (0 Auto, 1 Run)"
   },
   {
    "ref": "BV 2",
    "name": "externalStartCompressor1",
    "why": "Compressor 1 allow (0 Stop, 1 Auto)"
   },
   {
    "ref": "AV 35",
    "name": "flowTemperatureSetpointCom",
    "why": "Flow temperature setpoint, communicated mode"
   },
   {
    "ref": "BV 4",
    "name": "resetWatchdog",
    "why": "Third-party watchdog reset (5 min)"
   },
   {
    "ref": "MV 16",
    "name": "compressor1RunState",
    "why": "Compressor 1 run state"
   },
   {
    "ref": "AV 70",
    "name": "sensorT0",
    "why": "Heating system temperature T0"
   },
   {
    "ref": "AV 72",
    "name": "sensorTL1",
    "why": "Outdoor temperature (damped)"
   },
   {
    "ref": "BV 10",
    "name": "sumAlarmA",
    "why": "Summary alarm A"
   },
   {
    "ref": "BV 11",
    "name": "sumAlarmB",
    "why": "Summary alarm B"
   }
  ],
  "enable": "BV 1 (externalCompressorStartEnable) and BV 2/BV 3 (allow per compressor) let a third-party system start or block the compressors.",
  "heartbeat": "BV 4 resetWatchdog is the third-party watchdog reset (5 minutes); the Modbus part of the manual says watchdog-dependent settings are ignored unless the watchdog has been reset.",
  "remote_sensors": "BV 5 (CommunicatedSensors) switches T0 and TL1 to the values written to AV 3/AV 4; TW1 uses AV 5 when the TW1 sensor setting is Communicated. BV 6 (communicatedFlowTempSetpoint) makes the controller use the flow setpoint written to AV 35.",
  "setup": [
   "BACnet device instance is printed as 2001."
  ],
  "gotchas": [
   "MV 2 (AlaAcknow) and AV 2 (alarmAcknowledge) acknowledge alarms by writing the alarm number."
  ]
 },
 "points": [
  {
   "type": "AV",
   "instance": 2,
   "name": "alarmAcknowledge",
   "description": "Alarm acknowledge, write alarm numer to acknowledge alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "externalT0SensorValue",
   "description": "T0 sensor value in override mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "externalTL1SensorValue",
   "description": "TL1 sensor value in override mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "externalTW1SensorValue",
   "description": "TW1 sensor value in override mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Y_coordinate1",
   "description": "The heat curves value if the outdoor temperature is 20 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Y_coordinate2",
   "description": "The heat curves value if the outdoor temperature is 15 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Y_coordinate3",
   "description": "The heat curves value if the outdoor temperature is 10 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Y_coordinate4",
   "description": "The heat curves value if the outdoor temperature is 5 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Y_coordinate5",
   "description": "The heat curves value if the outdoor temperature is 0 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Y_coordinate6",
   "description": "The heat curves value if the outdoor temperature is -5 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "Y_coordinate7",
   "description": "The heat curves value if the outdoor temperature is -10 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "Y_coordinate8",
   "description": "The heat curves value if the outdoor temperature is -15 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Y_coordinate9",
   "description": "The heat curves value if the outdoor temperature is -20 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Y_coordinate10",
   "description": "The heat curves value if the outdoor temperature is -25 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Y_coordinate11",
   "description": "The heat curves value if the outdoor temperature is -30 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Y_coordinate12",
   "description": "The heat curves value if the outdoor temperature is -35 degrees",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "summerOperationTemperature",
   "description": "Start of summer operation temperature",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "summerOperationTime",
   "description": "Start of summer operation time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "winterOperationTemperature",
   "description": "Start of winter operation temperature",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "winterOperationTime",
   "description": "Start of winter operation time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "winterOperationNowTemperature",
   "description": "Imidiate start of winter operation temperature",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "dhwStartTemperatureCom",
   "description": "DHW TW1 start temperature if communicated TW1 sensor is used",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "dhwStopTemperatureCom",
   "description": "DHW TW1 stop temperature if communicated TW1 sensor is used",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "dhwStartTemperature",
   "description": "DHW TW1 start temperature if local TW1 sensor is used",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "dhwStopTemperature",
   "description": "DHW TW1 stop temperature if local TW1 sensor is used",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "addHeatStartHysteresis",
   "description": "additional heat start hysteresis",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "addHeatStartTime1",
   "description": "additional heat start time in degree minutes for step1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "addHeatStartTime2",
   "description": "additional heat start time in degree minutes for step2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "addHeatStartTime3",
   "description": "additional heat start time in degree minutes for step3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "addHeatStopTime1",
   "description": "additional heat stop time in degree minutes for step1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "addHeatStopTime2",
   "description": "additional heat stop time in degree minutes for step2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "addHeatStopTime3",
   "description": "additional heat stop time in degree minutes for step3",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "addHeatAlarmDelayTime",
   "description": "Delay time for additional heat alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "flowTemperatureSetpointCom",
   "description": "The flow temperature setpoint in communicated mode",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "fwsDhwCircPumpOffTimeWeekend",
   "description": "The FWS DHW curc. pump off time during weekends",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "fwsDhwCircPumpOnTimeWeekend",
   "description": "The FWS DHW curc. pump on time during weekends",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "fwsDhwCircPumpOffTimeWeekday",
   "description": "The FWS DHW curc. pump off time during weekdays",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "fwsDhwCircPumpOnTimeWeekday",
   "description": "The FWS DHW curc. pump on time during weekdays",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "fwsDhwAlarmHighDhwCircTemperatureLimit",
   "description": "The FWS Alarm limit for high DHW circ. temperature",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "fwsDhwAlarmHighDhwTemperatureLimit",
   "description": "The FWS Alarm limit for high DHW temperature",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "fwsDhwAlarmLowDhwCircTemperatureLimit",
   "description": "The FWS Alarm limit for low DHW circ. temperature",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "fwsDhwAlarmLowDhwTemperatureLimit",
   "description": "The FWS Alarm limit for low DHW temperature",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "fwsDhwHeatingWaterPumpTemperatureSetpoint",
   "description": "The FWS heating water pump DHW temperature setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "fwsDhwSetpoint",
   "description": "The FWS DHW setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "hybridControlElectricityPrice",
   "description": "Electricity price per kWh",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "hybridControlAddHeatPrice",
   "description": "Additional heat price per kWh",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "analogInput1",
   "description": "AI1, direct read (T0)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "analogInput2",
   "description": "AI2, direct read (TL1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "analogInput3",
   "description": "AI3, direct read (TW1)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "sensorT0",
   "description": "T0 sensor, heating system",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "sensorTL1Raw",
   "description": "TL1 sensor, outdoor direct",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "sensorTL1",
   "description": "TL1 sensor, outdoor damped",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "sensorTW1",
   "description": "TW1 sensor, DHW cylinder",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "sensorTR6",
   "description": "TR6 sensor, hotgas",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "sensorTC1",
   "description": "TC1 sensor, additional heat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "sensorTC0",
   "description": "TC0 sensor, heating return",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "sensorTB0",
   "description": "TB0 sensor, brine return",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "sensorTB1",
   "description": "TB1 sensor, brine flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "sensorTC2",
   "description": "TC2 sensor, buffer temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "sensorTR8",
   "description": "TR8 sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "sensorTC3",
   "description": "TC3 sensor, flow temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "sensorTR3",
   "description": "TR3 sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "sensorTR2",
   "description": "TR2 sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "sensorTR5",
   "description": "TR5 sensor",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "sensorTR7",
   "description": "TR7 sensor, hotgas",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "sensorJR0Temperature",
   "description": "JR0 sensor, temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "sensorJR0Pressure",
   "description": "JR0 sensor, pressure in bar",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "sensorJR1Temperature",
   "description": "JR1 sensor, temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "sensorJR1Pressure",
   "description": "JR1 sensor, pressure in bar",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "sensorJR2Temperature",
   "description": "JR2 sensor, temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "sensorJR2Pressure",
   "description": "JR2 sensor, pressure in bar",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "flowTemperatureSetpoint",
   "description": "Flow temperature setpoint for T0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "addHeatValve",
   "description": "Output for the additional heater valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "runTimeMeeterCompressor1",
   "description": "Run time meeter for compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "runTimeMeeterCompressor2",
   "description": "Run time meeter for compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "runTimeMeeterAddHeatStep1",
   "description": "Run time meeter for add heat step 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "runTimeMeeterAddHeatStep2",
   "description": "Run time meeter for add heat step 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "runTimeMeeterAddHeatStep3",
   "description": "Run time meeter for add heat step 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "runTimeMeeterPC1",
   "description": "Run time meeter for PC1 circ. pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "runTimeMeeterAddHeatValve",
   "description": "Run time meeter for Additional heater valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "runTimeMeeterSummaryAlarm",
   "description": "Run time meeter for the summary alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "runTimeMeeterDHW",
   "description": "Run time meeter for DHW",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "runTimeMeeterPC0",
   "description": "Run time meeter for PC0 heating pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "runTimeMeeterPB3",
   "description": "Run time meeter for PB3 brine pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "PC0Output",
   "description": "Current speed PC0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "PB3Output",
   "description": "Current speed PB3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "fwsDhwCircPump",
   "description": "FWS DHW circ. Pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "fwsDiverterValvePosition",
   "description": "FWS Diverter Valve Position",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "fwsHeatingWaterPump",
   "description": "FWS Heating Water Pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "fwsRunTimeMeeterDhwCirculationPump",
   "description": "FWS Run Time Meeter Dhw Circulation Pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "fwsColdWaterTemperature",
   "description": "FWS Cold Water Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "fwsSensorColdWaterTemperature",
   "description": "FWS Sensor Cold Water Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "fwsSensorDhwCircTemperature",
   "description": "FWS Sensor Dhw Circ Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "fwsSensorDhwFlowTemperature",
   "description": "FWS Sensor Dhw Flow Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "fwsSensorDhwReturnTemperature",
   "description": "FWS Sensor Dhw Return Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "fwsSensorHeatingFlowTemperature",
   "description": "FWS Sensor Heating Flow Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "fwsSensorHeatingReturnTemperature",
   "description": "FWS Sensor Heating Return Temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "fwsSensorWaterFlow",
   "description": "FWS Sensor Water Flow",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "fwsHeatingWaterPumpSpeed",
   "description": "FWS Heating Water Pump Speed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "summaryAlarmC_1",
   "description": "summary Alarm C_1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "summaryAlarmC_2",
   "description": "summary Alarm C_2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "summaryAlarmC_3",
   "description": "summary Alarm C_3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "summaryAlarmC_4",
   "description": "summary Alarm C_4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "summaryAlarmC_5",
   "description": "summary Alarm C_5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "externalCompressorStartEnable",
   "description": "Thirdpartie compressor start (0=Auto, 1=RUN)",
   "units": "",
   "access": "W",
   "states": "0=Auto, 1=RUN"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "externalStartCompressor1",
   "description": "Thirdpartie compressor allow (0=STOP, 1=Auto) for compressor1",
   "units": "",
   "access": "W",
   "states": "0=STOP, 1=Auto"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "externalStartCompressor2",
   "description": "Thirdpartie compressor allow (0=STOP, 1=Auto) for compressor2",
   "units": "",
   "access": "W",
   "states": "0=STOP, 1=Auto"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "resetWatchdog",
   "description": "Thirdpartie WatchDog reset (5 minutes)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "CommunicatedSensors",
   "description": "Override sensor inputs for T0 and TL1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "communicatedFlowTempSetpoint",
   "description": "Use communicated flow setpoint (AV 35); printed as 'Override sensor input for T0'",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "bootMode",
   "description": "Unit was just powered on",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "temporaryProtection",
   "description": "Temporary protection triggered",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "blockingProtection",
   "description": "blocking protection, needs reset",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "sumAlarmA",
   "description": "summary alarm, A",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "sumAlarmB",
   "description": "summary alarm, B",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "dhwValve",
   "description": "DHW valve VW1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "digitalInput1",
   "description": "Digital input 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "digitalInput2",
   "description": "Digital input 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "digitalInput3",
   "description": "Digital input 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "digitalInput4",
   "description": "Digital input 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "digitalInput5",
   "description": "Digital input 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "digitalInput6",
   "description": "Digital input 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "digitalInput7",
   "description": "Digital input 7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "digitalInput8",
   "description": "Digital input 8",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "digitalOutputPC0",
   "description": "Digital output PC0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "digitalOutputEE1",
   "description": "Digital output EE1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "digitalOutputEE2",
   "description": "Digital output EE2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "digitalOutputVW1",
   "description": "Digital output VW1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "digitalOutputPC1",
   "description": "Digital output PC1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "digitalOutputPM1",
   "description": "Digital output PM1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "digitalOutputSSM",
   "description": "Digital output SSM",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "digitalOutputCompressor1",
   "description": "Digital output compressor1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "digitalOutputCompressor2",
   "description": "Digital output compressor2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "digitalOutputER3",
   "description": "Digital output ER3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "digitalOutputER4",
   "description": "Digital output ER4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "externalDhwCircPumpTimeChannelEnable",
   "description": "External Circ. Pump DHW time channel (0=inactive, 1=active)",
   "units": "",
   "access": "W",
   "states": "0=inactive, 1=active"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "hybridControlHeatingEnable",
   "description": "Heating hybrid control (0=inactive, 1=active)",
   "units": "",
   "access": "W",
   "states": "0=inactive, 1=active"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "hybridControlDhwEnable",
   "description": "DHW hybrid control (0=inactive, 1=active)",
   "units": "",
   "access": "W",
   "states": "0=inactive, 1=active"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "AlaAcknow",
   "description": "Alarm acknowledge, write alarm numer to acknowledge alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "fwsDhwCircPumpOffTimeWeekend1",
   "description": "The FWS DHW curc. pump off time during weekends",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "numberOfStandardAccessories",
   "description": "Number of standard accessories installed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "additionalHeaterType",
   "description": "Which type of additional heat is installed",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "selectCompAddHeat",
   "description": "Which combination of heating is used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "warmWaterType",
   "description": "Which type of warmwater sensor is used",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "addHeatDemand",
   "description": "Current additional heat demand",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "compressor1Demand",
   "description": "Current demand state of compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "compressor1RunState",
   "description": "Current run state of compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "compressor2Demand",
   "description": "Current demand state of compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "compressor2RunState",
   "description": "Current run state of compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "Alarm1",
   "description": "Oper. error all PC1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 20,
   "name": "Alarm2",
   "description": "Oper. error compr. and add. heat",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 21,
   "name": "Alarm3",
   "description": "Failure on sensor T0 and TC2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 22,
   "name": "Alarm4",
   "description": "Sensor error TW4 DHW flowtemp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 23,
   "name": "Alarm5",
   "description": "Failure PC4 Heating water pump",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 24,
   "name": "Alarm10",
   "description": "Failure on sensor TR3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 25,
   "name": "Alarm11",
   "description": "Failure on sensor TW1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 26,
   "name": "Alarm12",
   "description": "Failure on sensor TC0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 27,
   "name": "Alarm13",
   "description": "Failure on sensor TC2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 28,
   "name": "Alarm14",
   "description": "Failure on sensor TC3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 29,
   "name": "Alarm15",
   "description": "Failure on sensor TB0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 30,
   "name": "Alarm16",
   "description": "Failure on sensor TB1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 31,
   "name": "Alarm17",
   "description": "Failure on sensor TR2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 32,
   "name": "Alarm18",
   "description": "Failure on sensor TR5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 33,
   "name": "Alarm19",
   "description": "Failure on sensor JR0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 34,
   "name": "Alarm20",
   "description": "Failure on sensor JR1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 35,
   "name": "Alarm21",
   "description": "Communication error with HP-card",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 36,
   "name": "Alarm22",
   "description": "Oper. error compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 37,
   "name": "Alarm23",
   "description": "Oper. error compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 38,
   "name": "Alarm24",
   "description": "Operating error PB3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 39,
   "name": "Alarm25",
   "description": "Low temperature JR0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 40,
   "name": "Alarm26",
   "description": "Tripped high pressure switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 41,
   "name": "Alarm27",
   "description": "Operating error PC0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 42,
   "name": "Alarm28",
   "description": "Internal add. heater overheated",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 43,
   "name": "Alarm29",
   "description": "Mixed add. heater doesn’t get warm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 44,
   "name": "Alarm30",
   "description": "Compressor 1 does not start",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 45,
   "name": "Alarm31",
   "description": "Compressor 2 does not start",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 46,
   "name": "Alarm32",
   "description": "High pressure JR1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 47,
   "name": "Alarm33",
   "description": "Low pressure JR1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 48,
   "name": "Alarm34",
   "description": "Low temperature TB0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 49,
   "name": "Alarm35",
   "description": "Low temperature TB1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 50,
   "name": "Alarm36",
   "description": "High temperature TB0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 51,
   "name": "Alarm37",
   "description": "High temperature TB1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 52,
   "name": "Alarm38",
   "description": "High temperature TR6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 53,
   "name": "Alarm39",
   "description": "High temperature TR7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 54,
   "name": "Alarm40",
   "description": "High temperature TC1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 55,
   "name": "Alarm41",
   "description": "High temperature TC0",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 56,
   "name": "Alarm42",
   "description": "Low temperature TR5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 57,
   "name": "Alarm43",
   "description": "Problem with hot water production",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 58,
   "name": "Alarm44",
   "description": "Problem with VW1 3-way valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 59,
   "name": "Alarm45",
   "description": "Problem with Zx VWx 3-way valve",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 60,
   "name": "Alarm46",
   "description": "Start-up attempt interrupted",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 61,
   "name": "Alarm47",
   "description": "Wrong rotation compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 62,
   "name": "Alarm48",
   "description": "Wrong rotation compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 63,
   "name": "Alarm49",
   "description": "Operating error PC1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 64,
   "name": "Alarm50",
   "description": "Compressor 1 overheated",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 65,
   "name": "Alarm51",
   "description": "Compressor 2 overheated",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 66,
   "name": "Alarm52",
   "description": "Communication error with accessory 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 67,
   "name": "Alarm53",
   "description": "Communication error with accessory 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 68,
   "name": "Alarm54",
   "description": "Communication error with accessory 3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 69,
   "name": "Alarm55",
   "description": "Communication error with accessory 4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 70,
   "name": "Alarm56",
   "description": "Communication error with accessory 5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 71,
   "name": "Alarm57",
   "description": "Communication error with accessory 6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 72,
   "name": "Alarm58",
   "description": "Communication error with accessory 7",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 73,
   "name": "Alarm59",
   "description": "Communication error with accessory 8",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 74,
   "name": "Alarm60",
   "description": "Communication error with accessory 9",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 75,
   "name": "Alarm61",
   "description": "Access.1 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 76,
   "name": "Alarm62",
   "description": "Access.2 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 77,
   "name": "Alarm63",
   "description": "Access.3 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 78,
   "name": "Alarm64",
   "description": "Access.4 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 79,
   "name": "Alarm65",
   "description": "Access.5 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 80,
   "name": "Alarm66",
   "description": "Access.6 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 81,
   "name": "Alarm67",
   "description": "Access.7 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 82,
   "name": "Alarm68",
   "description": "Access.8 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 83,
   "name": "Alarm69",
   "description": "Access.9 pump out of order",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 84,
   "name": "Alarm70",
   "description": "Communication error with Z1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 85,
   "name": "Alarm71",
   "description": "Communication error with Z2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 86,
   "name": "Alarm72",
   "description": "Communication error with Z3",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 87,
   "name": "Alarm73",
   "description": "Communication error with Z4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 88,
   "name": "Alarm74",
   "description": "Communication error with Z5",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 89,
   "name": "Alarm75",
   "description": "Compressor 1 overcurrent",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 90,
   "name": "Alarm76",
   "description": "Compressor 1 stall",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 91,
   "name": "Alarm77",
   "description": "Bypass relay 1 failure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 92,
   "name": "Alarm78",
   "description": "Wrong phase order on power supply",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 93,
   "name": "Alarm79",
   "description": "Wrong frequency order on power supply",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 94,
   "name": "Alarm80",
   "description": "Soft starter 1 faliure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 95,
   "name": "Alarm81",
   "description": "Fuse tripped for compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 96,
   "name": "Alarm82",
   "description": "Fuse tripped for compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 97,
   "name": "Alarm83",
   "description": "Wrong phase order to compressor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 98,
   "name": "Alarm84",
   "description": "Wrong phase order to compressor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 99,
   "name": "Alarm85",
   "description": "Wrong frequency to comperssor 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 100,
   "name": "Alarm86",
   "description": "Wrong frequency to comperssor 2",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 101,
   "name": "Alarm87",
   "description": "Compressor 2 overcurrent",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 102,
   "name": "Alarm88",
   "description": "Compressor 2 stall",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 103,
   "name": "Alarm89",
   "description": "Bypass relay 2 faliure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 104,
   "name": "Alarm90",
   "description": "Soft starter 2 faliure",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 105,
   "name": "Alarm91",
   "description": "TW4 sensor error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 107,
   "name": "Alarm93",
   "description": "TW5 sensor error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 108,
   "name": "Alarm94",
   "description": "Low temperature TW6",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 109,
   "name": "Alarm95",
   "description": "Low temperature TW4",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 110,
   "name": "Alarm96",
   "description": "The software in the HP-card is too old",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 111,
   "name": "Alarm97",
   "description": "The SW in the Regin box is too old",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 112,
   "name": "Alarm98",
   "description": "TW2 sensor error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 113,
   "name": "Alarm99",
   "description": "TW3 sensor error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 118,
   "name": "Alarm100",
   "description": "GW0 sensor error",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 119,
   "name": "Alarm101",
   "description": "TW4 high temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 120,
   "name": "Alarm102",
   "description": "TW2 low temperature",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 121,
   "name": "Alarm103",
   "description": "The software in the FWS is too old",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 122,
   "name": "Alarm104",
   "description": "The Regin SW is too old for the FWS",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 123,
   "name": "Alarm105",
   "description": "Communication error with FWS",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/bosch/rego-5200-heat-pump-controller",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}