 "manufacturer": "Advantage Controls",
 "manufacturer_slug": "advantage-controls",
 "model": "MegaTron Controller (BACnet H22)",
 "model_slug": "megatron-bacnet-h22",
 "short_model": "MegaTron H22",
 "aliases": [
  "MegaTron",
  "Megatron",
  "MegaTron BACnet",
  "BACnet H22",
  "M-BACnet H22",
  "Advantage Controls MegaTron"
 ],
 "equipment_type": "Water treatment controller",
 "applies_to": "Advantage Controls MegaTron water treatment controllers (cooling tower and boiler water chemistry) with the BACnet H22 option, software JA.16.0 and higher.",
 "summary": "The MegaTron is a multi-system water treatment controller for cooling towers and boilers. With the H22 option it is a BACnet IP device that reports conductivity, pH, ORP, temperatures, water and flow meter totals and 4-20 mA inputs for up to four systems, plus several hundred alarm flags. Setpoints, alarm limits, timer run times, mA outputs and relay states are writable.",
 "bacnet_transport": [
  "BACnet IP"
 ],
 "firmware": "JA.16.0 and higher",
 "default_device_instance": null,
 "access_inferred": false,
 "notes": [
  "Object names in the manual are generic (BI-000, BV-011, AI-008 ...); what each object means is in the Purpose column, shown here as the description.",
  "Instances start at 0. Most points repeat for System #1 to #4; objects marked \"Future Use\" are reserved.",
  "The object list gives no engineering units; values follow the units configured in the controller.",
  "Relay state MSVs use the printed states 1=H-OFF, 2=H-ON, 3=OFF, 4=ON.",
  "Access is from the \"Present Value - Access\" column: all BI, BV and AI objects are read-only; AV and MSV objects are read/write."
 ],
 "source": {
  "title": "MegaTron Controller Supplemental BACnet H22 Communications Manual",
  "doc_number": "M-BACnet H22",
  "revision_date": "03/2021",
  "url": "https://advantagecontrols.com/downloads/pdf/M-BACnet_H22.pdf"
 },
 "integration": {
  "summary": "Read the chemistry inputs (conductivity, pH, ORP) and the flow switch for each system in use, and map BV 301 All Alarms for a single summary alarm. Setpoints and alarm limits (AV objects) can be adjusted from the BMS if the owner wants that.",
  "minimum_points": [
   {
    "ref": "AV 0",
    "name": "AV-000",
    "why": "System 1 conductivity setpoint 1"
   },
   {
    "ref": "AI 0",
    "name": "AI-000",
    "why": "System 1 conductivity"
   },
   {
    "ref": "AI 8",
    "name": "AI-008",
    "why": "System 1 pH"
   },
   {
    "ref": "AI 12",
    "name": "AI-012",
    "why": "System 1 ORP"
   },
   {
    "ref": "BI 0",
    "name": "BI-000",
    "why": "System 1 flow switch"
   },
   {
    "ref": "BV 301",
    "name": "BV-301",
    "why": "Any active alarm"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "BACnet IP only (Annex J), on the same Ethernet port used for the WebAdvantage service.",
   "Set the device instance in Configure > Network settings > BAC; 4194303 means unconfigured. UDP port 47808 is shown on the same screen.",
   "The BMS must be on the same subnet as the MegaTron, or routing must be set up for BACnet traffic.",
   "Protocol revision 6, B-ASC; ReadProperty only (DS-RP-B), so polling is one property per request."
  ],
  "gotchas": [
   "The conformance summary lists only DS-RP-B (no WriteProperty BIBB) although AV and MSV objects are marked Read / Write; test writes on site before relying on them.",
   "Relay state MSVs (H-OFF, H-ON, OFF, ON) are marked Read / Write; check what a write does on site before mapping them as commands.",
   "Writing setpoints and alarm limits changes the controller configuration; avoid cyclic writes.",
   "Points exist for four systems whether or not they are installed."
  ]
 },
 "points": [
  {
   "type": "BI",
   "instance": 0,
   "name": "BI-000",
   "description": "System #1 – Flow Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 1,
   "name": "BI-001",
   "description": "System #2 – Flow Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "BI-002",
   "description": "System #3 – Flow Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "BI-003",
   "description": "System #4 – Flow Switch",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "BV-000",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "BV-001",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "BV-002",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "BV-003",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "BV-004",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "BV-005",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 6,
   "name": "BV-006",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "BV-007",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "BV-008",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "BV-009",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "BV-010",
   "description": "System #1 – Timer 5 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "BV-011",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "BV-012",
   "description": "System #1 – Conductivity High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "BV-013",
   "description": "System #1 – Conductivity Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "BV-014",
   "description": "System #1 – Conductivity Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 15,
   "name": "BV-015",
   "description": "System #1 – pH High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 16,
   "name": "BV-016",
   "description": "System #1 – pH Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "BV-017",
   "description": "System #1 – pH Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "BV-018",
   "description": "System #1 – ORP High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "BV-019",
   "description": "System #1 – ORP Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "BV-020",
   "description": "System #1 – ORP Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "BV-021",
   "description": "System #1 – S. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 22,
   "name": "BV-022",
   "description": "System #1 – S. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 23,
   "name": "BV-023",
   "description": "System #1 – M. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "BV-024",
   "description": "System #1 – M. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "BV-025",
   "description": "System #1 – D. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "BV-026",
   "description": "System #1 – D. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "BV-027",
   "description": "System #1 – No Flow Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "BV-028",
   "description": "System #1 – Digital Input 1 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "BV-029",
   "description": "System #1 – Digital Input 2 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "BV-030",
   "description": "System #1 – Digital Input 3 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "BV-031",
   "description": "System #1 – Digital Input 4 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "BV-032",
   "description": "System #1 – Digital Input 5 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "BV-033",
   "description": "System #1 – M. Conductivity Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "BV-034",
   "description": "System #1 – M. Conductivity High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "BV-035",
   "description": "System #1 – M. Conductivity Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "BV-036",
   "description": "System #1 – M. Conductivity Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "BV-037",
   "description": "System #1 – Notepad 1 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 38,
   "name": "BV-038",
   "description": "System #1 – Notepad 2 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "BV-039",
   "description": "System #1 – Notepad 3 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "BV-040",
   "description": "System #1 – Notepad 4 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 41,
   "name": "BV-041",
   "description": "System #1 – Notepad 5 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 42,
   "name": "BV-042",
   "description": "System #1 – Notepad 6 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 43,
   "name": "BV-043",
   "description": "System #1 – Notepad 7 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 44,
   "name": "BV-044",
   "description": "System #1 – Notepad 8 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 45,
   "name": "BV-045",
   "description": "System #1 – Notepad 9 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 46,
   "name": "BV-046",
   "description": "System #1 – Notepad 10 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 47,
   "name": "BV-047",
   "description": "System #1 – Notepad 1 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 48,
   "name": "BV-048",
   "description": "System #1 – Notepad 2 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 49,
   "name": "BV-049",
   "description": "System #1 – Notepad 3 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 50,
   "name": "BV-050",
   "description": "System #1 – Notepad 4 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 51,
   "name": "BV-051",
   "description": "System #1 – Notepad 5 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 52,
   "name": "BV-052",
   "description": "System #1 – Notepad 6 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 53,
   "name": "BV-053",
   "description": "System #1 – Notepad 7 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 54,
   "name": "BV-054",
   "description": "System #1 – Notepad 8 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 55,
   "name": "BV-055",
   "description": "System #1 – Notepad 9 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 56,
   "name": "BV-056",
   "description": "System #1 – Notepad 10 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 57,
   "name": "BV-057",
   "description": "System #1 – Notepad 1 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 58,
   "name": "BV-058",
   "description": "System #1 – Notepad 2 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 59,
   "name": "BV-059",
   "description": "System #1 – Notepad 3 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 60,
   "name": "BV-060",
   "description": "System #1 – Notepad 4 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 61,
   "name": "BV-061",
   "description": "System #1 – Notepad 5 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 62,
   "name": "BV-062",
   "description": "System #1 – Notepad 6 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 63,
   "name": "BV-063",
   "description": "System #1 – Notepad 7 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 64,
   "name": "BV-064",
   "description": "System #1 – Notepad 8 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 65,
   "name": "BV-065",
   "description": "System #1 – Notepad 9 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 66,
   "name": "BV-066",
   "description": "System #1 – Notepad 10 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 67,
   "name": "BV-067",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 68,
   "name": "BV-068",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 69,
   "name": "BV-069",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 70,
   "name": "BV-070",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 71,
   "name": "BV-071",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 72,
   "name": "BV-072",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 73,
   "name": "BV-073",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 74,
   "name": "BV-074",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 75,
   "name": "BV-075",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 76,
   "name": "BV-076",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 77,
   "name": "BV-077",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 78,
   "name": "BV-078",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 79,
   "name": "BV-079",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 80,
   "name": "BV-080",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 81,
   "name": "BV-081",
   "description": "System #2 – Conductivity High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 82,
   "name": "BV-082",
   "description": "System #2 – Conductivity Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 83,
   "name": "BV-083",
   "description": "System #2 – Conductivity Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 84,
   "name": "BV-084",
   "description": "System #2 – pH High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 85,
   "name": "BV-085",
   "description": "System #2 – pH Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 86,
   "name": "BV-086",
   "description": "System #2 – pH Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 87,
   "name": "BV-087",
   "description": "System #2 – ORP High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 88,
   "name": "BV-088",
   "description": "System #2 – ORP Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 89,
   "name": "BV-089",
   "description": "System #2 – ORP Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 90,
   "name": "BV-090",
   "description": "System #2 – S. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 91,
   "name": "BV-091",
   "description": "System #2 – S. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 92,
   "name": "BV-092",
   "description": "System #2 – M. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 93,
   "name": "BV-093",
   "description": "System #2 – M. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 94,
   "name": "BV-094",
   "description": "System #2 – D. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 95,
   "name": "BV-095",
   "description": "System #2 – D. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 96,
   "name": "BV-096",
   "description": "System #2 – No Flow Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 97,
   "name": "BV-097",
   "description": "System #2 – Digital Input 1 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 98,
   "name": "BV-098",
   "description": "System #2 – Digital Input 2 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 99,
   "name": "BV-099",
   "description": "System #2 – Digital Input 3 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 100,
   "name": "BV-100",
   "description": "System #2 – Digital Input 4 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 101,
   "name": "BV-101",
   "description": "System #2 – Digital Input 5 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 102,
   "name": "BV-102",
   "description": "System #2 – M. Conductivity Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 103,
   "name": "BV-103",
   "description": "System #2 – M. Conductivity High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 104,
   "name": "BV-104",
   "description": "System #2 – M. Conductivity Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 105,
   "name": "BV-105",
   "description": "System #2 – M. Conductivity Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 106,
   "name": "BV-106",
   "description": "System #2 – Notepad 1 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 107,
   "name": "BV-107",
   "description": "System #2 – Notepad 2 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 108,
   "name": "BV-108",
   "description": "System #2 – Notepad 3 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 109,
   "name": "BV-109",
   "description": "System #2 – Notepad 4 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 110,
   "name": "BV-110",
   "description": "System #2 – Notepad 5 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 111,
   "name": "BV-111",
   "description": "System #2 – Notepad 6 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 112,
   "name": "BV-112",
   "description": "System #2 – Notepad 7 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 113,
   "name": "BV-113",
   "description": "System #2 – Notepad 8 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 114,
   "name": "BV-114",
   "description": "System #2 – Notepad 9 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 115,
   "name": "BV-115",
   "description": "System #2 – Notepad 10 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 116,
   "name": "BV-116",
   "description": "System #2 – Notepad 1 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 117,
   "name": "BV-117",
   "description": "System #2 – Notepad 2 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 118,
   "name": "BV-118",
   "description": "System #2 – Notepad 3 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 119,
   "name": "BV-119",
   "description": "System #2 – Notepad 4 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 120,
   "name": "BV-120",
   "description": "System #2 – Notepad 5 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 121,
   "name": "BV-121",
   "description": "System #2 – Notepad 6 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 122,
   "name": "BV-122",
   "description": "System #2 – Notepad 7 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 123,
   "name": "BV-123",
   "description": "System #2 – Notepad 8 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 124,
   "name": "BV-124",
   "description": "System #2 – Notepad 9 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 125,
   "name": "BV-125",
   "description": "System #2 – Notepad 10 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 126,
   "name": "BV-126",
   "description": "System #2 – Notepad 1 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 127,
   "name": "BV-127",
   "description": "System #2 – Notepad 2 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 128,
   "name": "BV-128",
   "description": "System #2 – Notepad 3 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 129,
   "name": "BV-129",
   "description": "System #2 – Notepad 4 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 130,
   "name": "BV-130",
   "description": "System #2 – Notepad 5 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 131,
   "name": "BV-131",
   "description": "System #2 – Notepad 6 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 132,
   "name": "BV-132",
   "description": "System #2 – Notepad 7 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 133,
   "name": "BV-133",
   "description": "System #2 – Notepad 8 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 134,
   "name": "BV-134",
   "description": "System #2 – Notepad 9 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 135,
   "name": "BV-135",
   "description": "System #2 – Notepad 10 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 136,
   "name": "BV-136",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 137,
   "name": "BV-137",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 138,
   "name": "BV-138",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 139,
   "name": "BV-139",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 140,
   "name": "BV-140",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 141,
   "name": "BV-141",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 142,
   "name": "BV-142",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 143,
   "name": "BV-143",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 144,
   "name": "BV-144",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 145,
   "name": "BV-145",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 146,
   "name": "BV-146",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 147,
   "name": "BV-147",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 148,
   "name": "BV-148",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 149,
   "name": "BV-149",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 150,
   "name": "BV-150",
   "description": "System #3 – Conductivity High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 151,
   "name": "BV-151",
   "description": "System #3 – Conductivity Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 152,
   "name": "BV-152",
   "description": "System #3 – Conductivity Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 153,
   "name": "BV-153",
   "description": "System #3 – pH High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 154,
   "name": "BV-154",
   "description": "System #3 – pH Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 155,
   "name": "BV-155",
   "description": "System #3 – pH Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 156,
   "name": "BV-156",
   "description": "System #3 – ORP High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 157,
   "name": "BV-157",
   "description": "System #3 – ORP Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 158,
   "name": "BV-158",
   "description": "System #3 – ORP Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 159,
   "name": "BV-159",
   "description": "System #3 – S. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 160,
   "name": "BV-160",
   "description": "System #3 – S. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 161,
   "name": "BV-161",
   "description": "System #3 – M. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 162,
   "name": "BV-162",
   "description": "System #3 – M. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 163,
   "name": "BV-163",
   "description": "System #3 – D. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 164,
   "name": "BV-164",
   "description": "System #3 – D. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 165,
   "name": "BV-165",
   "description": "System #3 – No Flow Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 166,
   "name": "BV-166",
   "description": "System #3 – Digital Input 1 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 167,
   "name": "BV-167",
   "description": "System #3 – Digital Input 2 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 168,
   "name": "BV-168",
   "description": "System #3 – Digital Input 3 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 169,
   "name": "BV-169",
   "description": "System #3 – Digital Input 4 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 170,
   "name": "BV-170",
   "description": "System #3 – Digital Input 5 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 171,
   "name": "BV-171",
   "description": "System #3 – M. Conductivity Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 172,
   "name": "BV-172",
   "description": "System #3 – M. Conductivity High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 173,
   "name": "BV-173",
   "description": "System #3 – M. Conductivity Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 174,
   "name": "BV-174",
   "description": "System #3 – M. Conductivity Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 175,
   "name": "BV-175",
   "description": "System #3 – Notepad 1 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 176,
   "name": "BV-176",
   "description": "System #3 – Notepad 2 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 177,
   "name": "BV-177",
   "description": "System #3 – Notepad 3 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 178,
   "name": "BV-178",
   "description": "System #3 – Notepad 4 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 179,
   "name": "BV-179",
   "description": "System #3 – Notepad 5 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 180,
   "name": "BV-180",
   "description": "System #3 – Notepad 6 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 181,
   "name": "BV-181",
   "description": "System #3 – Notepad 7 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 182,
   "name": "BV-182",
   "description": "System #3 – Notepad 8 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 183,
   "name": "BV-183",
   "description": "System #3 – Notepad 9 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 184,
   "name": "BV-184",
   "description": "System #3 – Notepad 10 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 185,
   "name": "BV-185",
   "description": "System #3 – Notepad 1 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 186,
   "name": "BV-186",
   "description": "System #3 – Notepad 2 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 187,
   "name": "BV-187",
   "description": "System #3 – Notepad 3 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 188,
   "name": "BV-188",
   "description": "System #3 – Notepad 4 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 189,
   "name": "BV-189",
   "description": "System #3 – Notepad 5 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 190,
   "name": "BV-190",
   "description": "System #3 – Notepad 6 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 191,
   "name": "BV-191",
   "description": "System #3 – Notepad 7 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 192,
   "name": "BV-192",
   "description": "System #3 – Notepad 8 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 193,
   "name": "BV-193",
   "description": "System #3 – Notepad 9 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 194,
   "name": "BV-194",
   "description": "System #3 – Notepad 10 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 195,
   "name": "BV-195",
   "description": "System #3 – Notepad 1 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 196,
   "name": "BV-196",
   "description": "System #3 – Notepad 2 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 197,
   "name": "BV-197",
   "description": "System #3 – Notepad 3 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 198,
   "name": "BV-198",
   "description": "System #3 – Notepad 4 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 199,
   "name": "BV-199",
   "description": "System #3 – Notepad 5 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 200,
   "name": "BV-200",
   "description": "System #3 – Notepad 6 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 201,
   "name": "BV-201",
   "description": "System #3 – Notepad 7 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 202,
   "name": "BV-202",
   "description": "System #3 – Notepad 8 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 203,
   "name": "BV-203",
   "description": "System #3 – Notepad 9 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 204,
   "name": "BV-204",
   "description": "System #3 – Notepad 10 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 205,
   "name": "BV-205",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 206,
   "name": "BV-206",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 207,
   "name": "BV-207",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 208,
   "name": "BV-208",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 209,
   "name": "BV-209",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 210,
   "name": "BV-210",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 211,
   "name": "BV-211",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 212,
   "name": "BV-212",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 213,
   "name": "BV-213",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 214,
   "name": "BV-214",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 215,
   "name": "BV-215",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 216,
   "name": "BV-216",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 217,
   "name": "BV-217",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 218,
   "name": "BV-218",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 219,
   "name": "BV-219",
   "description": "System #4 – Conductivity High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 220,
   "name": "BV-220",
   "description": "System #4 – Conductivity Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 221,
   "name": "BV-221",
   "description": "System #4 – Conductivity Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 222,
   "name": "BV-222",
   "description": "System #4 – pH High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 223,
   "name": "BV-223",
   "description": "System #4 – pH Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 224,
   "name": "BV-224",
   "description": "System #4 – pH Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 225,
   "name": "BV-225",
   "description": "System #4 – ORP High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 226,
   "name": "BV-226",
   "description": "System #4 – ORP Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 227,
   "name": "BV-227",
   "description": "System #4 – ORP Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 228,
   "name": "BV-228",
   "description": "System #4 – S. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 229,
   "name": "BV-229",
   "description": "System #4 – S. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 230,
   "name": "BV-230",
   "description": "System #4 – M. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 231,
   "name": "BV-231",
   "description": "System #4 – M. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 232,
   "name": "BV-232",
   "description": "System #4 – D. Temp High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 233,
   "name": "BV-233",
   "description": "System #4 – D. Temp Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 234,
   "name": "BV-234",
   "description": "System #4 – No Flow Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 235,
   "name": "BV-235",
   "description": "System #4 – Digital Input 1 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 236,
   "name": "BV-236",
   "description": "System #4 – Digital Input 2 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 237,
   "name": "BV-237",
   "description": "System #4 – Digital Input 3 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 238,
   "name": "BV-238",
   "description": "System #4 – Digital Input 4 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 239,
   "name": "BV-239",
   "description": "System #4 – Digital Input 5 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 240,
   "name": "BV-240",
   "description": "System #4 – M. Conductivity Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 241,
   "name": "BV-241",
   "description": "System #4 – M. Conductivity High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 242,
   "name": "BV-242",
   "description": "System #4 – M. Conductivity Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 243,
   "name": "BV-243",
   "description": "System #4 – M. Conductivity Limit Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 244,
   "name": "BV-244",
   "description": "System #4 – Notepad 1 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 245,
   "name": "BV-245",
   "description": "System #4 – Notepad 2 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 246,
   "name": "BV-246",
   "description": "System #4 – Notepad 3 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 247,
   "name": "BV-247",
   "description": "System #4 – Notepad 4 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 248,
   "name": "BV-248",
   "description": "System #4 – Notepad 5 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 249,
   "name": "BV-249",
   "description": "System #4 – Notepad 6 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 250,
   "name": "BV-250",
   "description": "System #4 – Notepad 7 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 251,
   "name": "BV-251",
   "description": "System #4 – Notepad 8 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 252,
   "name": "BV-252",
   "description": "System #4 – Notepad 9 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 253,
   "name": "BV-253",
   "description": "System #4 – Notepad 10 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 254,
   "name": "BV-254",
   "description": "System #4 – Notepad 1 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 255,
   "name": "BV-255",
   "description": "System #4 – Notepad 2 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 256,
   "name": "BV-256",
   "description": "System #4 – Notepad 3 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 257,
   "name": "BV-257",
   "description": "System #4 – Notepad 4 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 258,
   "name": "BV-258",
   "description": "System #4 – Notepad 5 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 259,
   "name": "BV-259",
   "description": "System #4 – Notepad 6 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 260,
   "name": "BV-260",
   "description": "System #4 – Notepad 7 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 261,
   "name": "BV-261",
   "description": "System #4 – Notepad 8 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 262,
   "name": "BV-262",
   "description": "System #4 – Notepad 9 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 263,
   "name": "BV-263",
   "description": "System #4 – Notepad 10 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 264,
   "name": "BV-264",
   "description": "System #4 – Notepad 1 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 265,
   "name": "BV-265",
   "description": "System #4 – Notepad 2 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 266,
   "name": "BV-266",
   "description": "System #4 – Notepad 3 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 267,
   "name": "BV-267",
   "description": "System #4 – Notepad 4 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 268,
   "name": "BV-268",
   "description": "System #4 – Notepad 5 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 269,
   "name": "BV-269",
   "description": "System #4 – Notepad 6 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 270,
   "name": "BV-270",
   "description": "System #4 – Notepad 7 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 271,
   "name": "BV-271",
   "description": "System #4 – Notepad 8 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 272,
   "name": "BV-272",
   "description": "System #4 – Notepad 9 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 273,
   "name": "BV-273",
   "description": "System #4 – Notepad 10 Time Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 274,
   "name": "BV-274",
   "description": "System #4 – pH 2 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 275,
   "name": "BV-275",
   "description": "System #4 – ORP 2 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 276,
   "name": "BV-276",
   "description": "ma Input 1 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 277,
   "name": "BV-277",
   "description": "ma Input 1 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 278,
   "name": "BV-278",
   "description": "ma Input 1 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 279,
   "name": "BV-279",
   "description": "ma Input 2 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 280,
   "name": "BV-280",
   "description": "ma Input 2 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 281,
   "name": "BV-281",
   "description": "ma Input 2 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 282,
   "name": "BV-282",
   "description": "ma Input 3 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 283,
   "name": "BV-283",
   "description": "ma Input 3 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 284,
   "name": "BV-284",
   "description": "ma Input 3 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 285,
   "name": "BV-285",
   "description": "ma Input 4 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 286,
   "name": "BV-286",
   "description": "ma Input 4 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 287,
   "name": "BV-287",
   "description": "ma Input 4 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 288,
   "name": "BV-288",
   "description": "ma Input 5 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 289,
   "name": "BV-289",
   "description": "ma Input 5 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 290,
   "name": "BV-290",
   "description": "ma Input 5 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 291,
   "name": "BV-291",
   "description": "ma Input 6 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 292,
   "name": "BV-292",
   "description": "ma Input 6 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 293,
   "name": "BV-293",
   "description": "ma Input 6 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 294,
   "name": "BV-294",
   "description": "ma Input 7 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 295,
   "name": "BV-295",
   "description": "ma Input 7 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 296,
   "name": "BV-296",
   "description": "ma Input 7 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 297,
   "name": "BV-297",
   "description": "ma Input 8 Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 298,
   "name": "BV-298",
   "description": "ma Input 8 High Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 299,
   "name": "BV-299",
   "description": "ma Input 8 Low Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 300,
   "name": "BV-300",
   "description": "Utility",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 301,
   "name": "BV-301",
   "description": "All Alarms",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 302,
   "name": "BV-302",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 303,
   "name": "BV-303",
   "description": "Flow Meter 1 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 304,
   "name": "BV-304",
   "description": "Flow Meter 1 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 305,
   "name": "BV-305",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 306,
   "name": "BV-306",
   "description": "Flow Meter 2 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 307,
   "name": "BV-307",
   "description": "Flow Meter 2 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 308,
   "name": "BV-308",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 309,
   "name": "BV-309",
   "description": "Flow Meter 3 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 310,
   "name": "BV-310",
   "description": "Flow Meter 3 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 311,
   "name": "BV-311",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 312,
   "name": "BV-312",
   "description": "Flow Meter 4 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 313,
   "name": "BV-313",
   "description": "Flow Meter 4 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 314,
   "name": "BV-314",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 315,
   "name": "BV-315",
   "description": "Flow Meter 5 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 316,
   "name": "BV-316",
   "description": "Flow Meter 5 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 317,
   "name": "BV-317",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 318,
   "name": "BV-318",
   "description": "Flow Meter 6 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 319,
   "name": "BV-319",
   "description": "Flow Meter 6 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 320,
   "name": "BV-320",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 321,
   "name": "BV-321",
   "description": "Flow Meter 7 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 322,
   "name": "BV-322",
   "description": "Flow Meter 7 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 323,
   "name": "BV-323",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 324,
   "name": "BV-324",
   "description": "Flow Meter 8 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 325,
   "name": "BV-325",
   "description": "Flow Meter 8 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 326,
   "name": "BV-326",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 327,
   "name": "BV-327",
   "description": "Flow Meter 9 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 328,
   "name": "BV-328",
   "description": "Flow Meter 9 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 329,
   "name": "BV-329",
   "description": "Future Use",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 330,
   "name": "BV-330",
   "description": "Flow Meter 10 Flow Verify",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 331,
   "name": "BV-331",
   "description": "Flow Meter 10 Volume Alarm",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 332,
   "name": "BV-332",
   "description": "Relay 1 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 333,
   "name": "BV-333",
   "description": "Relay 2 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 334,
   "name": "BV-334",
   "description": "Relay 3 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 335,
   "name": "BV-335",
   "description": "Relay 4 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 336,
   "name": "BV-336",
   "description": "Relay 5 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 337,
   "name": "BV-337",
   "description": "Relay 6 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 338,
   "name": "BV-338",
   "description": "Relay 7 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 339,
   "name": "BV-339",
   "description": "Relay 8 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 340,
   "name": "BV-340",
   "description": "Relay 9 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 341,
   "name": "BV-341",
   "description": "Relay 10 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 342,
   "name": "BV-342",
   "description": "Relay 11 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 343,
   "name": "BV-343",
   "description": "Relay 12 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 344,
   "name": "BV-344",
   "description": "Relay 13 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 345,
   "name": "BV-345",
   "description": "Relay 14 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 346,
   "name": "BV-346",
   "description": "Relay 15 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 347,
   "name": "BV-347",
   "description": "Relay 16 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 348,
   "name": "BV-348",
   "description": "Relay 17 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 349,
   "name": "BV-349",
   "description": "Relay 18 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 350,
   "name": "BV-350",
   "description": "Relay 19 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 351,
   "name": "BV-351",
   "description": "Relay 20 Max Hours",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 352,
   "name": "BV-352",
   "description": "mA Input 1 Limit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 353,
   "name": "BV-353",
   "description": "mA Input 2 Limit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 354,
   "name": "BV-354",
   "description": "mA Input 3 Limit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 355,
   "name": "BV-355",
   "description": "mA Input 4 Limit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 356,
   "name": "BV-356",
   "description": "mA Input 5 Limit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 357,
   "name": "BV-357",
   "description": "mA Input 6 Limit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 358,
   "name": "BV-358",
   "description": "mA Input 7 Limit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "BV",
   "instance": 359,
   "name": "BV-359",
   "description": "mA Input 8 Limit",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "AI-000",
   "description": "System #1 – Conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "AI-001",
   "description": "System #2 – Conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 2,
   "name": "AI-002",
   "description": "System #3 – Conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 3,
   "name": "AI-003",
   "description": "System #4 – Conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 4,
   "name": "AI-004",
   "description": "System #1 – M. Conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 5,
   "name": "AI-005",
   "description": "System #2 – M. Conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 6,
   "name": "AI-006",
   "description": "System #3 – M. Conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 7,
   "name": "AI-007",
   "description": "System #4 – M. Conductivity",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 8,
   "name": "AI-008",
   "description": "System #1 – pH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 9,
   "name": "AI-009",
   "description": "System #2 – pH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 10,
   "name": "AI-010",
   "description": "System #3 – pH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 11,
   "name": "AI-011",
   "description": "System #4 – pH",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 12,
   "name": "AI-012",
   "description": "System #1 – ORP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 13,
   "name": "AI-013",
   "description": "System #2 – ORP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 14,
   "name": "AI-014",
   "description": "System #3 – ORP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 15,
   "name": "AI-015",
   "description": "System #4 – ORP",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 16,
   "name": "AI-016",
   "description": "System #1 – S. Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 17,
   "name": "AI-017",
   "description": "System #2 – S. Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 18,
   "name": "AI-018",
   "description": "System #3 – S. Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 19,
   "name": "AI-019",
   "description": "System #4 – S. Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 20,
   "name": "AI-020",
   "description": "System #1 – M. Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 21,
   "name": "AI-021",
   "description": "System #2 – M. Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 22,
   "name": "AI-022",
   "description": "System #3 – M. Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 23,
   "name": "AI-023",
   "description": "System #4 – M. Temp",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 24,
   "name": "AI-024",
   "description": "Sys #1 – Water Meter #1 - Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 25,
   "name": "AI-025",
   "description": "Sys #2 – Water Meter #1 - Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 26,
   "name": "AI-026",
   "description": "Sys #3 – Water Meter #1 - Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 27,
   "name": "AI-027",
   "description": "Sys #4 – Water Meter #1 - Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 28,
   "name": "AI-028",
   "description": "Sys #1 – Water Meter #2 - Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 29,
   "name": "AI-029",
   "description": "Sys #2 – Water Meter #2 - Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 30,
   "name": "AI-030",
   "description": "Sys #3 – Water Meter #2 - Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 31,
   "name": "AI-031",
   "description": "Sys #4 – Water Meter #2 - Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 32,
   "name": "AI-032",
   "description": "System #1 – M.Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 33,
   "name": "AI-033",
   "description": "System #2 – M.Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 34,
   "name": "AI-034",
   "description": "System #3 – M.Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 35,
   "name": "AI-035",
   "description": "System #4 – M.Cycles",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 36,
   "name": "AI-036",
   "description": "4-20 mA / 0-5V Input #1 - Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 37,
   "name": "AI-037",
   "description": "4-20 mA / 0-5V Input #2 - Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 38,
   "name": "AI-038",
   "description": "4-20 mA / 0-5V Input #3 - Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 39,
   "name": "AI-039",
   "description": "4-20 mA / 0-5V Input #4 - Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 40,
   "name": "AI-040",
   "description": "4-20 mA / 0-5V Input #5 - Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 41,
   "name": "AI-041",
   "description": "4-20 mA / 0-5V Input #6 - Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 42,
   "name": "AI-042",
   "description": "4-20 mA / 0-5V Input #7 - Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 43,
   "name": "AI-043",
   "description": "4-20 mA / 0-5V Input #8 - Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 44,
   "name": "AI-044",
   "description": "Flow Meter #1 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 45,
   "name": "AI-045",
   "description": "Flow Meter #2 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 46,
   "name": "AI-046",
   "description": "Flow Meter #3 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 47,
   "name": "AI-047",
   "description": "Flow Meter #4 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 48,
   "name": "AI-048",
   "description": "Flow Meter #5 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 49,
   "name": "AI-049",
   "description": "Flow Meter #6 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 50,
   "name": "AI-050",
   "description": "Flow Meter #7 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 51,
   "name": "AI-051",
   "description": "Flow Meter #8 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 52,
   "name": "AI-052",
   "description": "Flow Meter #9 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 53,
   "name": "AI-053",
   "description": "Flow Meter #10 – Total Value",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 54,
   "name": "AI-054",
   "description": "Flow Meter #1 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 55,
   "name": "AI-055",
   "description": "Flow Meter #2 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 56,
   "name": "AI-056",
   "description": "Flow Meter #3 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 57,
   "name": "AI-057",
   "description": "Flow Meter #4 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 58,
   "name": "AI-058",
   "description": "Flow Meter #5 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 59,
   "name": "AI-059",
   "description": "Flow Meter #6 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 60,
   "name": "AI-060",
   "description": "Flow Meter #7 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 61,
   "name": "AI-061",
   "description": "Flow Meter #8 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 62,
   "name": "AI-062",
   "description": "Flow Meter #9 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 63,
   "name": "AI-063",
   "description": "Flow Meter #10 – Flow Rate (per MIN)",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "AV-000",
   "description": "System #1 – Conductivity Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "AV-001",
   "description": "System #2 – Conductivity Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "AV-002",
   "description": "System #3 – Conductivity Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "AV-003",
   "description": "System #4 – Conductivity Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "AV-004",
   "description": "System #1 – Conductivity Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "AV-005",
   "description": "System #2 – Conductivity Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "AV-006",
   "description": "System #3 – Conductivity Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "AV-007",
   "description": "System #4 – Conductivity Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "AV-008",
   "description": "System #1 – Conductivity High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "AV-009",
   "description": "System #2 – Conductivity High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "AV-010",
   "description": "System #3 – Conductivity High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "AV-011",
   "description": "System #4 – Conductivity High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "AV-012",
   "description": "System #1 – Conductivity Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 13,
   "name": "AV-013",
   "description": "System #2 – Conductivity Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "AV-014",
   "description": "System #3 – Conductivity Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "AV-015",
   "description": "System #4 – Conductivity Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "AV-016",
   "description": "System #1 – M. Conductivity Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "AV-017",
   "description": "System #2 – M. Conductivity Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "AV-018",
   "description": "System #3 – M. Conductivity Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "AV-019",
   "description": "System #4 – M. Conductivity Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "AV-020",
   "description": "System #1 – M. Conductivity High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "AV-021",
   "description": "System #2 – M. Conductivity High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 22,
   "name": "AV-022",
   "description": "System #3 – M. Conductivity High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "AV-023",
   "description": "System #4 – M. Conductivity High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "AV-024",
   "description": "System #1 – M. Conductivity Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "AV-025",
   "description": "System #2 – M. Conductivity Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "AV-026",
   "description": "System #3 – M. Conductivity Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 27,
   "name": "AV-027",
   "description": "System #4 – M. Conductivity Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 28,
   "name": "AV-028",
   "description": "System #1 – pH Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "AV-029",
   "description": "System #2 – pH Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "AV-030",
   "description": "System #3 – pH Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "AV-031",
   "description": "System #4 – pH Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "AV-032",
   "description": "System #1 – pH Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "AV-033",
   "description": "System #2 – pH Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "AV-034",
   "description": "System #3 – pH Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 35,
   "name": "AV-035",
   "description": "System #4 – pH Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 36,
   "name": "AV-036",
   "description": "System #1 – pH High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 37,
   "name": "AV-037",
   "description": "System #2 – pH High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 38,
   "name": "AV-038",
   "description": "System #3 – pH High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 39,
   "name": "AV-039",
   "description": "System #4 – pH High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "AV-040",
   "description": "System #1 – pH Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "AV-041",
   "description": "System #2 – pH Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "AV-042",
   "description": "System #3 – pH Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "AV-043",
   "description": "System #4 – pH Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "AV-044",
   "description": "System #1 – ORP Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "AV-045",
   "description": "System #2 – ORP Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "AV-046",
   "description": "System #3 – ORP Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 47,
   "name": "AV-047",
   "description": "System #4 – ORP Setpoint #1",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 48,
   "name": "AV-048",
   "description": "System #1 – ORP Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "AV-049",
   "description": "System #2 – ORP Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 50,
   "name": "AV-050",
   "description": "System #3 – ORP Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 51,
   "name": "AV-051",
   "description": "System #4 – ORP Setpoint #2",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 52,
   "name": "AV-052",
   "description": "System #1 – ORP High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "AV-053",
   "description": "System #2 – ORP High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "AV-054",
   "description": "System #3 – ORP High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "AV-055",
   "description": "System #4 – ORP High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 56,
   "name": "AV-056",
   "description": "System #1 – ORP Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 57,
   "name": "AV-057",
   "description": "System #2 – ORP Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 58,
   "name": "AV-058",
   "description": "System #3 – ORP Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 59,
   "name": "AV-059",
   "description": "System #4 – ORP Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 60,
   "name": "AV-060",
   "description": "System #1 – S. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 61,
   "name": "AV-061",
   "description": "System #2 – S. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 62,
   "name": "AV-062",
   "description": "System #3 – S. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 63,
   "name": "AV-063",
   "description": "System #4 – S. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 64,
   "name": "AV-064",
   "description": "System #1 – S. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 65,
   "name": "AV-065",
   "description": "System #2 – S. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 66,
   "name": "AV-066",
   "description": "System #3 – S. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 67,
   "name": "AV-067",
   "description": "System #4 – S. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 68,
   "name": "AV-068",
   "description": "System #1 – S. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 69,
   "name": "AV-069",
   "description": "System #2 – S. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 70,
   "name": "AV-070",
   "description": "System #3 – S. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 71,
   "name": "AV-071",
   "description": "System #4 – S. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 72,
   "name": "AV-072",
   "description": "System #1 – M. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 73,
   "name": "AV-073",
   "description": "System #2 – M. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 74,
   "name": "AV-074",
   "description": "System #3 – M. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 75,
   "name": "AV-075",
   "description": "System #4 – M. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 76,
   "name": "AV-076",
   "description": "System #1 – M. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 77,
   "name": "AV-077",
   "description": "System #2 – M. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 78,
   "name": "AV-078",
   "description": "System #3 – M. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 79,
   "name": "AV-079",
   "description": "System #4 – M. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 80,
   "name": "AV-080",
   "description": "System #1 – M. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 81,
   "name": "AV-081",
   "description": "System #2 – M. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 82,
   "name": "AV-082",
   "description": "System #3 – M. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 83,
   "name": "AV-083",
   "description": "System #4 – M. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 84,
   "name": "AV-084",
   "description": "System #1 – D. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 85,
   "name": "AV-085",
   "description": "System #2 – D. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 86,
   "name": "AV-086",
   "description": "System #3 – D. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 87,
   "name": "AV-087",
   "description": "System #4 – D. Temp Setpoint",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 88,
   "name": "AV-088",
   "description": "System #1 – D. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 89,
   "name": "AV-089",
   "description": "System #2 – D. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 90,
   "name": "AV-090",
   "description": "System #3 – D. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 91,
   "name": "AV-091",
   "description": "System #4 – D. Temp High Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 92,
   "name": "AV-092",
   "description": "System #1 – D. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 93,
   "name": "AV-093",
   "description": "System #2 – D. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 94,
   "name": "AV-094",
   "description": "System #3 – D. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 95,
   "name": "AV-095",
   "description": "System #4 – D. Temp Low Alarm",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 96,
   "name": "AV-096",
   "description": "System #1 – Flow Switch Conf.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 97,
   "name": "AV-097",
   "description": "System #2 – Flow Switch Conf.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 98,
   "name": "AV-098",
   "description": "System #3 – Flow Switch Conf.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 99,
   "name": "AV-099",
   "description": "System #4 – Flow Switch Conf.",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 100,
   "name": "AV-100",
   "description": "mA 1 - Output Value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 101,
   "name": "AV-101",
   "description": "mA 2 - Output Value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 102,
   "name": "AV-102",
   "description": "mA 3 - Output Value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 103,
   "name": "AV-103",
   "description": "mA 4 - Output Value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 104,
   "name": "AV-104",
   "description": "mA 5 - Output Value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 105,
   "name": "AV-105",
   "description": "mA 6 - Output Value",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 106,
   "name": "AV-106",
   "description": "System #1 - Timer #1 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 107,
   "name": "AV-107",
   "description": "System #1 - Timer #2 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 108,
   "name": "AV-108",
   "description": "System #1 - Timer #3 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 109,
   "name": "AV-109",
   "description": "System #1 - Timer #4 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 110,
   "name": "AV-110",
   "description": "System #1 - Timer #5 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 111,
   "name": "AV-111",
   "description": "System #2 - Timer #1 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 112,
   "name": "AV-112",
   "description": "System #2 - Timer #2 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 113,
   "name": "AV-113",
   "description": "System #2 - Timer #3 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 114,
   "name": "AV-114",
   "description": "System #2 - Timer #4 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 115,
   "name": "AV-115",
   "description": "System #2 - Timer #5 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 116,
   "name": "AV-116",
   "description": "System #3 - Timer #1 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 117,
   "name": "AV-117",
   "description": "System #3 - Timer #2 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 118,
   "name": "AV-118",
   "description": "System #3 - Timer #3 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 119,
   "name": "AV-119",
   "description": "System #3 - Timer #4 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "AV-120",
   "description": "System #3 - Timer #5 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "AV-121",
   "description": "System #4 - Timer #1 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "AV-122",
   "description": "System #4 - Timer #2 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "AV-123",
   "description": "System #4 - Timer #3 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "AV-124",
   "description": "System #4 - Timer #4 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "AV-125",
   "description": "System #4 - Timer #5 - Run Time",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "MSV-000",
   "description": "Relay 1 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "MSV-001",
   "description": "Relay 2 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "MSV-002",
   "description": "Relay 3 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "MSV-003",
   "description": "Relay 4 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "MSV-004",
   "description": "Relay 5 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "MSV-005",
   "description": "Relay 6 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "MSV-006",
   "description": "Relay 7 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 7,
   "name": "MSV-007",
   "description": "Relay 8 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 8,
   "name": "MSV-008",
   "description": "Relay 9 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 9,
   "name": "MSV-009",
   "description": "Relay 10 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 10,
   "name": "MSV-010",
   "description": "Relay 11 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 11,
   "name": "MSV-011",
   "description": "Relay 12 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 12,
   "name": "MSV-012",
   "description": "Relay 13 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 13,
   "name": "MSV-013",
   "description": "Relay 14 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 14,
   "name": "MSV-014",
   "description": "Relay 15 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 15,
   "name": "MSV-015",
   "description": "Relay 16 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 16,
   "name": "MSV-016",
   "description": "Relay 17 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 17,
   "name": "MSV-017",
   "description": "Relay 18 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 18,
   "name": "MSV-018",
   "description": "Relay 19 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  },
  {
   "type": "MV",
   "instance": 19,
   "name": "MSV-019",
   "description": "Relay 20 – State",
   "units": "",
   "access": "W",
   "states": "1=H-OFF, 2=H-ON, 3=OFF, 4=ON"
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/advantage-controls/megatron-bacnet-h22",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}