 "manufacturer": "ABB",
 "manufacturer_slug": "abb",
 "model": "ACH180 HVAC drive (embedded BACnet MS/TP)",
 "model_slug": "ach180",
 "aliases": [
  "ACH180",
  "ACH180-01",
  "ACH180 HVAC control program",
  "3AXD50000955893"
 ],
 "equipment_type": "Variable frequency drive (HVAC)",
 "applies_to": "ABB ACH180 compact HVAC drives using the built-in EFB (RS-485) port with protocol set to BACnet MS/TP.",
 "summary": "The ACH180 is ABB's compact HVAC drive with BACnet MS/TP built into its EFB terminal (X5), enabled with parameter 58.01. Its fixed object list covers relay, digital I/O and analog I/O status, run/stop, direction and permissive commands, two speed references, energy counters, fault and warning history, a process PID loop and ten user-mapped Data-IO values.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "HVAC control program 2.20.0.0 (AHVDC)",
 "default_device_instance": 4194303,
 "access_inferred": false,
 "notes": [
  "Set the device instance with parameter 58.40 Device object ID (1-4194303); it must be unique on the network.",
  "Commands (BV10-BV14, AV16/AV17) only take effect when the drive's start/reference sources are set to embedded fieldbus.",
  "AV120-AV129 (Data-IO-1..10) carry whatever drive parameters are mapped in 58.101-58.110; Data-IO-5..10 are read-only.",
  "Gaps in the instance numbering are reserved by ABB and do not exist on the drive.",
  "MSV1-MSV3 state lists print 'Output-Phase-Loss Motor-Stall' without a comma; split here into two states, numbered 1..n in printed order.",
  "Loop objects (LOOP0/LOOP1) point at AV44 output, AV43 feedback and AV42 setpoint."
 ],
 "source": {
  "title": "ACH180 HVAC control program Firmware manual",
  "doc_number": "3AXD50000955893 Rev B",
  "revision_date": "2024-03-28",
  "url": "https://library.e.abb.com/public/f3d8d50ec8db4a54baecad8c3ec97ca1/EN_ACH180_FW_B_A5.pdf"
 },
 "integration": {
  "summary": "Set 58.01 Protocol enable = BACnet MSTP, then 58.03 node address, 58.04 baud and 58.40 Device object ID, save with 96.07 and apply with 58.06 Refresh settings. Point 20.01 Ext1 commands at Embedded fieldbus and the Ext1 frequency or speed reference (28.11 or 22.11) at EFB ref1, then command BV10 and AV16. Configure 58.14-58.16 so the drive reacts to a lost BMS.",
  "minimum_points": [
   {
    "ref": "BV 10",
    "name": "RUN-STOP-Command",
    "why": "Start/stop from the BMS"
   },
   {
    "ref": "AV 16",
    "name": "Input-Reference-1",
    "why": "Speed reference in %"
   },
   {
    "ref": "BV 14",
    "name": "Fault-Reset-Command",
    "why": "Reset a tripped drive"
   },
   {
    "ref": "BV 0",
    "name": "RUN-STOP-Monitor",
    "why": "Running status"
   },
   {
    "ref": "BV 4",
    "name": "HAND-AUTO-Monitor",
    "why": "Shows if the panel has the drive in Hand"
   },
   {
    "ref": "AV 1",
    "name": "Output-Freq",
    "why": "Output frequency in Hz"
   },
   {
    "ref": "AV 4",
    "name": "Output-Current",
    "why": "Motor amps"
   },
   {
    "ref": "AV 6",
    "name": "Output-Power",
    "why": "Drive power in kW"
   },
   {
    "ref": "BV 2",
    "name": "OK-FAULT-Monitor",
    "why": "Any active drive fault"
   },
   {
    "ref": "MV 1",
    "name": "Active-Fault-1",
    "why": "Which fault is active"
   }
  ],
  "enable": "Set 20.01 Ext1 commands (and 20.06 Ext2) to Embedded fieldbus so BV10 starts and stops the drive; 20.21 Direction = Request lets BV11 set direction. For the reference set 28.11 Ext1 frequency ref1 = EFB ref1 (scalar mode, the default) or 22.11 Ext1 speed ref1 = EFB ref1 (vector) for AV16; ref2 / AV17 uses 28.15 or 22.18. 19.11 = EFB MCW bit 11 lets BV13 pick Ext1/Ext2. BV18 Control-Override-Command also gives BACnet control; panel HAND mode has priority.",
  "heartbeat": "BACnet itself has no timeout. 58.14 Communication loss action (No action, Fault, Last speed, Speed ref safe, Fault always, Warning), 58.15 Communication loss mode (Any message or Cw/Ref1/Ref2) and 58.16 Communication loss time (0-6000 s) define the reaction. Changes need a reboot or 58.06 Refresh settings.",
  "remote_sensors": "For the process PID set its feedback and setpoint sources to the data storage parameters 40.91 / 40.92, then write AV43 LOOP-Feedback and AV42 LOOP-Setpoint. AO0 drives analog output 1 when 13.12 AO1 source = AO1 data storage, and BO0/BO5 drive RO1/DO1 when their source is an RO/DIO control word bit.",
  "setup": [
   "58.01 Protocol enable = BACnet MSTP turns on the EFB port (terminal X5).",
   "58.03 Node address and 58.04 Baud rate set the MS/TP link.",
   "58.40 Device object ID sets the device instance (unique, 1-4194303); the device object's default is 4194303.",
   "Save with 96.07 Parameter save manually and apply with 58.06 Communication control = Refresh settings.",
   "58.07-58.13 are diagnostic counters for checking the link."
  ],
  "gotchas": [
   "Panel HAND mode beats BACnet control override (BV18).",
   "BV39 Parameter-Save-Command writes permanent memory; use it once, not cyclically.",
   "Last speed and Speed ref safe keep the motor running after a comm loss; make sure that is safe.",
   "Fault reset through BV14 always goes through; no source parameter is needed.",
   "AV120-AV129 Data-IO objects only carry data after parameters 58.101-58.110 are mapped."
  ]
 },
 "points": [
  {
   "type": "BI",
   "instance": 0,
   "name": "RO1-Monitor",
   "description": "Status of relay output 1",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "DO1-Monitor",
   "description": "Status of digital output 1",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BI",
   "instance": 6,
   "name": "DI1-Monitor",
   "description": "Status of digital input 1",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BI",
   "instance": 7,
   "name": "DI2-Monitor",
   "description": "Status of digital input 2",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BI",
   "instance": 8,
   "name": "DI3-Monitor",
   "description": "Status of digital input 3",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BI",
   "instance": 9,
   "name": "DI4-Monitor",
   "description": "Status of digital input 4",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BI",
   "instance": 10,
   "name": "DI5-Monitor",
   "description": "Status of digital input 5",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BO",
   "instance": 0,
   "name": "RO1-Command",
   "description": "Output state of relay 1",
   "units": "",
   "access": "C",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BO",
   "instance": 5,
   "name": "DO1-Command",
   "description": "Output state of digital output 1",
   "units": "",
   "access": "C",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 0,
   "name": "RUN-STOP-Monitor",
   "description": "Drive’s run status",
   "units": "",
   "access": "R",
   "states": "Active: Run, Inactive: Stop"
  },
  {
   "type": "BV",
   "instance": 1,
   "name": "Direction-Monitor",
   "description": "Rotational direction of the motor",
   "units": "",
   "access": "R",
   "states": "Active: Reverse, Inactive: Forward"
  },
  {
   "type": "BV",
   "instance": 2,
   "name": "OK-FAULT-Monitor",
   "description": "Actual fault status of drive",
   "units": "",
   "access": "R",
   "states": "Active: Fault, Inactive: OK"
  },
  {
   "type": "BV",
   "instance": 3,
   "name": "EXT1-EXT2-Monitor",
   "description": "Actual control source",
   "units": "",
   "access": "R",
   "states": "Active: Ext2, Inactive: Ext1"
  },
  {
   "type": "BV",
   "instance": 4,
   "name": "HAND-AUTO-Monitor",
   "description": "Actual operating mode",
   "units": "",
   "access": "R",
   "states": "Active: Hand, Inactive: Auto"
  },
  {
   "type": "BV",
   "instance": 5,
   "name": "Warning-Monitor",
   "description": "Actual warning status",
   "units": "",
   "access": "R",
   "states": "Active: Warning, Inactive: OK"
  },
  {
   "type": "BV",
   "instance": 7,
   "name": "Ready-Monitor",
   "description": "Actual ready status",
   "units": "",
   "access": "R",
   "states": "Active: Ready, Inactive: Not-Ready"
  },
  {
   "type": "BV",
   "instance": 8,
   "name": "At-Setpoint-Monitor",
   "description": "Actual at setpoint status",
   "units": "",
   "access": "R",
   "states": "Active: Yes, Inactive: No"
  },
  {
   "type": "BV",
   "instance": 9,
   "name": "Enabled-Monitor",
   "description": "Actual run enabled status",
   "units": "",
   "access": "R",
   "states": "Active: Enable, Inactive: Disable"
  },
  {
   "type": "BV",
   "instance": 10,
   "name": "RUN-STOP-Command",
   "description": "Command to start drive",
   "units": "",
   "access": "C",
   "states": "Active: Run, Inactive: Stop"
  },
  {
   "type": "BV",
   "instance": 11,
   "name": "Direction-Command",
   "description": "Command to rotational direction",
   "units": "",
   "access": "C",
   "states": "Active: Reverse, Inactive: Forward"
  },
  {
   "type": "BV",
   "instance": 12,
   "name": "Run-Permissive-Command",
   "description": "Command to run permissive command",
   "units": "",
   "access": "C",
   "states": "Active: Enable, Inactive: Disable"
  },
  {
   "type": "BV",
   "instance": 13,
   "name": "EXT1-EXT2-Command",
   "description": "Commanded to external 1 or external 2 selection",
   "units": "",
   "access": "C",
   "states": "Active: Ext2, Inactive: Ext1"
  },
  {
   "type": "BV",
   "instance": 14,
   "name": "Fault-Reset-Command",
   "description": "Commanded to fault reset",
   "units": "",
   "access": "W",
   "states": "Active: Reset, Inactive: No"
  },
  {
   "type": "BV",
   "instance": 17,
   "name": "Lock-Parameters",
   "description": "Actual status of parameter lock",
   "units": "",
   "access": "R",
   "states": "Active: Lock, Inactive: Unlock"
  },
  {
   "type": "BV",
   "instance": 18,
   "name": "Control-Override-Command",
   "description": "Put the drive in BACnet control override (HAND has priority)",
   "units": "",
   "access": "C",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 19,
   "name": "Control-Override-Monitor",
   "description": "Shows BACnet control override is active",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 20,
   "name": "Start-Interlock-1-Command",
   "description": "Command to start enable 1",
   "units": "",
   "access": "C",
   "states": "Active: Enable, Inactive: Disable"
  },
  {
   "type": "BV",
   "instance": 21,
   "name": "Start-Interlock-2-Command",
   "description": "Command to start enable 2",
   "units": "",
   "access": "C",
   "states": "Active: Enable, Inactive: Disable"
  },
  {
   "type": "BV",
   "instance": 24,
   "name": "Started-Monitor",
   "description": "Actual start status",
   "units": "",
   "access": "R",
   "states": "Active: Started, Inactive: Not-Started"
  },
  {
   "type": "BV",
   "instance": 25,
   "name": "Safe-Torque-Off-Monitor",
   "description": "Actual status of Safe Torque Off",
   "units": "",
   "access": "R",
   "states": "Active: Active, Inactive: OK"
  },
  {
   "type": "BV",
   "instance": 26,
   "name": "Underload-Monitor",
   "description": "Indicates if ULC signal is lower than the Underload curve",
   "units": "",
   "access": "R",
   "states": "Active: Underload, Inactive: OK"
  },
  {
   "type": "BV",
   "instance": 27,
   "name": "Overload-Monitor",
   "description": "Indicates if ULC signal is higher than the overload curve",
   "units": "",
   "access": "R",
   "states": "Active: Overload, Inactive: OK"
  },
  {
   "type": "BV",
   "instance": 28,
   "name": "Motor-Heating-Command",
   "description": "Command to motor heating mode",
   "units": "",
   "access": "W",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 29,
   "name": "Motor-Heating-Monitor",
   "description": "Actual status of motor heating mode",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 30,
   "name": "User0-Monitor",
   "description": "Actual status of “User bit0” in drive status word",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 31,
   "name": "User1-Monitor",
   "description": "Actual status of “User bit1” in drive status word",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 32,
   "name": "User2-Monitor",
   "description": "Actual status of “User bit2” in drive status word",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 33,
   "name": "User3-Monitor",
   "description": "Actual status of “User bit3” in drive status word",
   "units": "",
   "access": "R",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 34,
   "name": "User0-Command",
   "description": "Commands “User bit0” in drive status word",
   "units": "",
   "access": "C",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 35,
   "name": "User1-Command",
   "description": "Commands “User bit1” in drive status word",
   "units": "",
   "access": "C",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 36,
   "name": "User2-Command",
   "description": "Commands “User bit2” in drive status word",
   "units": "",
   "access": "C",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 37,
   "name": "User3-Command",
   "description": "Commands “User bit3” in drive status word",
   "units": "",
   "access": "C",
   "states": "Active: On, Inactive: Off"
  },
  {
   "type": "BV",
   "instance": 39,
   "name": "Parameter-Save-Command",
   "description": "Save drive parameters and persistent BACnet data",
   "units": "",
   "access": "W",
   "states": "Active: Save, Inactive: No"
  },
  {
   "type": "BV",
   "instance": 40,
   "name": "PID-Set-Select",
   "description": "Command to Process PID set1 or Process PID set2 selection",
   "units": "",
   "access": "W",
   "states": "Active: Set1, Inactive: Set2"
  },
  {
   "type": "AI",
   "instance": 0,
   "name": "AI1-Monitor",
   "description": "Indicates the input level of analog input 1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AI",
   "instance": 1,
   "name": "AI2-Monitor",
   "description": "Indicates the input level of analog input 2",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AO",
   "instance": 0,
   "name": "AO1-Command",
   "description": "Controls analog output 1 (drive must be configured for BACnet control)",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 0,
   "name": "Output-RPM",
   "description": "Motor speed",
   "units": "rpm",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Output-Freq",
   "description": "Output frequency",
   "units": "Hz",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "DC-Voltage",
   "description": "DC bus voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Output-Voltage",
   "description": "AC output voltage",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Output-Current",
   "description": "Output current of drive",
   "units": "A",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Output-Torque",
   "description": "Motor torque, % of nominal",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Output-Power",
   "description": "Output power in kW",
   "units": "kW",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Operating-Temp-Range",
   "description": "Heatsink temperature, % of fault limit",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Kilowatt-Hour-Meter-R",
   "description": "Resettable energy counter",
   "units": "kWh",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Kilowatt-Hour-Meter-NR",
   "description": "Non-resettable energy counter",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Process-PID-Feedback",
   "description": "This object is the process PID feedback signal",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "Process-PID-Deviation",
   "description": "Process PID deviation from setpoint",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 14,
   "name": "Running-Hours",
   "description": "Resettable run time (write 0 to reset)",
   "units": "h",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 15,
   "name": "Motor-Temp-Degrees-C",
   "description": "Motor temperature",
   "units": "°C",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 16,
   "name": "Input-Reference-1",
   "description": "Speed setpoint 1",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 17,
   "name": "Input-Reference-2",
   "description": "Speed setpoint 2",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 18,
   "name": "Active-Fault",
   "description": "Displays most recent fault currently active",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 19,
   "name": "Previous-Fault-1",
   "description": "Displays most recent stored (nonactive) fault",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 20,
   "name": "Previous-Fault-2",
   "description": "Displays the second most recent stored (non-active) fault",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 21,
   "name": "AO1-Monitor",
   "description": "Output level of analog output 1",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 23,
   "name": "Accel-1-Seconds",
   "description": "Ramp1 acceleration time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 24,
   "name": "Decel-1-Seconds",
   "description": "Ramp 1 deceleration time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 25,
   "name": "Mbox-Param",
   "description": "Parameter number to be used by mailbox function",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 26,
   "name": "Mbox-Data",
   "description": "Set (W) or indicate (R) of the data value of mailbox function",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 29,
   "name": "Min-Speed",
   "description": "Defines the allowed minimum output frequency",
   "units": "Hz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 30,
   "name": "Max-Speed",
   "description": "Defines the allowed maximum output frequency",
   "units": "Hz",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 31,
   "name": "Output-Speed",
   "description": "Actual motor speed",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 32,
   "name": "Output-Current-Range",
   "description": "Actual motor current",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 33,
   "name": "Max-Current",
   "description": "Max motor current",
   "units": "A",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 34,
   "name": "DC-ripple",
   "description": "Vp-p ripple on DC bus",
   "units": "V",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 40,
   "name": "LOOP-Feedback-Monitor",
   "description": "Loop feedback after source selection and filtering",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 41,
   "name": "LOOP-Setpoint-Monitor",
   "description": "Loop setpoint after source selection, limits and ramping",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 42,
   "name": "LOOP-Setpoint",
   "description": "Loop setpoint written by BACnet",
   "units": "%",
   "access": "C",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 43,
   "name": "LOOP-Feedback",
   "description": "Stores the feedback value for loop controller",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 44,
   "name": "LOOP-Output",
   "description": "Loop controller output",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 45,
   "name": "LOOP-Gain",
   "description": "Loop controller gain",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 46,
   "name": "LOOP-Integration-Time",
   "description": "Loop controller integration time",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 49,
   "name": "LOOP-Deviation-Monitor",
   "description": "Loop controller deviation",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 53,
   "name": "LOOP-1-Gain",
   "description": "Loop controller gain (set 2)",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 54,
   "name": "LOOP-1-Integration-Time",
   "description": "Loop controller integration time (set 2)",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 55,
   "name": "LOOP-2-Feedback-Monitor",
   "description": "External loop feedback after source selection and filtering",
   "units": "%",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 120,
   "name": "Data-IO-1",
   "description": "Value of the drive parameter mapped in 58.101",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 121,
   "name": "Data-IO-2",
   "description": "Value of the drive parameter mapped in 58.102",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 122,
   "name": "Data-IO-3",
   "description": "Value of the drive parameter mapped in 58.103",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 123,
   "name": "Data-IO-4",
   "description": "Value of the drive parameter mapped in 58.104",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 124,
   "name": "Data-IO-5",
   "description": "Value of the drive parameter mapped in 58.105",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 125,
   "name": "Data-IO-6",
   "description": "Value of the drive parameter mapped in 58.106",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 126,
   "name": "Data-IO-7",
   "description": "Value of the drive parameter mapped in 58.107",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 127,
   "name": "Data-IO-8",
   "description": "Value of the drive parameter mapped in 58.108",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 128,
   "name": "Data-IO-9",
   "description": "Value of the drive parameter mapped in 58.109",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 129,
   "name": "Data-IO-10",
   "description": "Value of the drive parameter mapped in 58.110",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 130,
   "name": "Kilowatt-Hour-This-Hour",
   "description": "Current hour energy consumption",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 131,
   "name": "Kilowatt-Hour-Last-Hour",
   "description": "Last hour energy consumption",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 132,
   "name": "Kilowatt-Hour-This-Day",
   "description": "Current day energy consumption",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 133,
   "name": "Kilowatt-Hour-Last-Day",
   "description": "Last day energy consumption",
   "units": "kWh",
   "access": "R",
   "states": ""
  },
  {
   "type": "MV",
   "instance": 0,
   "name": "HAND-AUTO-Reference",
   "description": "Hand, Auto, Off or Override control state",
   "units": "",
   "access": "R",
   "states": "1=Off, 2=Hand, 3=Auto, 4=Override"
  },
  {
   "type": "MV",
   "instance": 1,
   "name": "Active-Fault-1",
   "description": "Enumerated type of the most recent fault currently active",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Comm-Error, 3=Overcurrent, 4=Overtemperature, 5=Overspeed, 6=Overvoltage, 7=Undervoltage, 8=Short-Circuit, 9=Ground-Fault, 10=Motor-Overload, 11=Inverter-Overload, 12=Motor-Underload, 13=External-Fault, 14=Operator-Interface-Error, 15=Config-Error, 16=Feedback-Failure, 17=Output-Phase-Loss, 18=Motor-Stall, 19=Power-Unit-Error, 20=Input-Phase-Fault, 21=Internal-Failure, 22=STO-Active, 23=Other"
  },
  {
   "type": "MV",
   "instance": 2,
   "name": "Active-Fault-2",
   "description": "Enumerated type of the 2nd most recent fault currently active",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Comm-Error, 3=Overcurrent, 4=Overtemperature, 5=Overspeed, 6=Overvoltage, 7=Undervoltage, 8=Short-Circuit, 9=Ground-Fault, 10=Motor-Overload, 11=Inverter-Overload, 12=Motor-Underload, 13=External-Fault, 14=Operator-Interface-Error, 15=Config-Error, 16=Feedback-Failure, 17=Output-Phase-Loss, 18=Motor-Stall, 19=Power-Unit-Error, 20=Input-Phase-Fault, 21=Internal-Failure, 22=STO-Active, 23=Other"
  },
  {
   "type": "MV",
   "instance": 3,
   "name": "Active-Fault-3",
   "description": "Enumerated type of the 3rd most recent fault currently active",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Comm-Error, 3=Overcurrent, 4=Overtemperature, 5=Overspeed, 6=Overvoltage, 7=Undervoltage, 8=Short-Circuit, 9=Ground-Fault, 10=Motor-Overload, 11=Inverter-Overload, 12=Motor-Underload, 13=External-Fault, 14=Operator-Interface-Error, 15=Config-Error, 16=Feedback-Failure, 17=Output-Phase-Loss, 18=Motor-Stall, 19=Power-Unit-Error, 20=Input-Phase-Fault, 21=Internal-Failure, 22=STO-Active, 23=Other"
  },
  {
   "type": "MV",
   "instance": 4,
   "name": "Active-Warning-1",
   "description": "Enumerated type of the most recent warning currently active",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Comm-Error, 3=Current-Limit, 4=Overtemperature, 5=Start-Interlock-1, 6=Start-Interlock-2, 7=Start-Interlock-3, 8=Start-Interlock-4, 9=Run-Permissive, 10=Internal-Warning, 11=Start-Delay, 12=Other"
  },
  {
   "type": "MV",
   "instance": 5,
   "name": "Active-Warning-2",
   "description": "Enumerated type of the 2nd most recent warning currently active",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Comm-Error, 3=Current-Limit, 4=Overtemperature, 5=Start-Interlock-1, 6=Start-Interlock-2, 7=Start-Interlock-3, 8=Start-Interlock-4, 9=Run-Permissive, 10=Internal-Warning, 11=Start-Delay, 12=Other"
  },
  {
   "type": "MV",
   "instance": 6,
   "name": "Active-Warning-3",
   "description": "Enumerated type of the 3rd most recent warning currently active",
   "units": "",
   "access": "R",
   "states": "1=None, 2=Comm-Error, 3=Current-Limit, 4=Overtemperature, 5=Start-Interlock-1, 6=Start-Interlock-2, 7=Start-Interlock-3, 8=Start-Interlock-4, 9=Run-Permissive, 10=Internal-Warning, 11=Start-Delay, 12=Other"
  },
  {
   "type": "LO",
   "instance": 0,
   "name": "LOOP-Set1",
   "description": "Loop object for process PID set 1",
   "units": "",
   "access": "R",
   "states": ""
  },
  {
   "type": "LO",
   "instance": 1,
   "name": "LOOP-Set2",
   "description": "Loop object for process PID set 2",
   "units": "",
   "access": "R",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/abb/ach180",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}